Safety Shutdown Reason Codes - Honeywell FlexLine SmartServo 954 Service Manual

Servo-based level gauge
Hide thumbs Also See for FlexLine SmartServo 954:
Table of Contents

Advertisement

COMMISSIONING

7.3.13.2 Safety Shutdown Reason Codes

The Safety Function Status Codes listed below have detail error information in the
output's Safety Shutdown Reason entity.
Safety Function
Safety Shutdown Reason Codes
Status Code
BOARD
VOLTAGE MON ADC ERROR
FAILURE
Communication with the FII-SIL voltage monitor failed
VOLTAGE MON POWER SUPPLY LO LIM_EXCEEDED
The power supply voltage is below the lower limit.
VOLTAGE MON POWER SUPPLY HI_LIM_EXCEEDED
The power supply voltage is above the upper limit.
VOLTAGE MON LOGIC LO LIM EXCEEDED
The internal voltage VDD1 is below the lower limit.
VOLTAGE MON LOGIC HI LIM EXCEEDED
The internal voltage VDD1 is above the upper limit.
VOLTAGE MON CAN TRANSMITTER LO LIM EXCEEDED
The internal voltage VDD3 is below the lower limit.
VOLTAGE MON CAN TRANSMITTER HI LIM EXCEEDED
The internal voltage VDD3 is above the upper limit.
HARDWARE VERSION VOLTAGE OUT OF RANGE
The FII-SIL hardware version is invalid
FUNCTION
SIL OUTPUT SELF-TEST FAILURE
FAILURE
The output function health diagnostics have failed.
CODE
ROM ERROR
CHECKSUM
The FII-SIL firmware is corrupted.
FAILURE
BOARD
TEMPERATURE MON LO LIM EXCEEDED
TEMPERATURE
The FII-SIL module temperature is below the lower limit
FAILURE
TEMPERATURE MON HI LIM EXCEEDED
The FII-SIL module temperature is above the upper limit
TEMPSENS SPI COMMUNICATION ERROR
Communication with the FII-SIL module temperature sensor failed.