COMMISSIONING
Name
[Alarm test enable]
[Alarm test]
[Element wiring]
[Function identification]
Name
[Gas immersion depth]
[High High alarm]
[High Alarm]
[Low Alarm]
[Low Low alarm]
124
Explanation
Enables (if activated, see
next listed entity) the
simulation of one of the 4
alarms for a minute, by
simulating the actual
measured Primary Value is
below or above the alarm
threshold.
Activates and selects at the
same time the Alarm test (if
enabled with the
enable]
listed before, and the
4 alarm thresholds are
properly set).
Used for excluding an
element from the average
product temperature
calculation.
The current module's
function name. This
function is visible on the
HART SmartView
display.

Vapour Temperature

NOTE: Using Engauge, following entities are set within the Engauge
Vapour temperature tab. Some Vapour temperature settings are
shared with Product temperature settings.
The following entities can be set by Engauge or HART SmartView for a
correct functioning of the FII-VT module in an instrument.
Check each entity for its correctness.
Explanation
The minimum required
distance below an element
before it is taken into
account in the average
Vapour temperature
calculation
4 thresholds for activating a
related alarm status in the
Primary Value
Service Manual
954 SmartServo FlexLine
Value Range
<enable>
<disable>
[No Alarm]
[High High alarm]
[Alarm test
[High Alarm]
[Low Alarm]
[Low Low alarm]
16 characters
A non-zero (
at position
x
element
x
being excluded
from calculation.
13 characters
Value Range
floating point number:
<-x.x .. +x.x>
floating point number:
<-x.x .. +x.x>
Default
<disable>
<No Alarm>
<0000000000000000>
0) character
results in
<Product temp.>
Default
<0.5>
<+1.0E22>
Part No.: 4417340 Revision 1