Engauge * Ambient Temperature * Tab - Honeywell FlexLine SmartServo 954 Service Manual

Servo-based level gauge
Hide thumbs Also See for FlexLine SmartServo 954:
Table of Contents

Advertisement

COMMISSIONING
Name
[High High
alarm] [High
Alarm]
[Low Alarm]
[Low Low alarm]
[Alarm test enable]
[Alarm test]
[Function identification]
7.3.8.4.5
Part No.: 4417340 Revision 1

Engauge * Ambient temperature * Tab

NOTE: Some settings for ambient temperature calculations are
shared via the product temperature settings.
The following entities can be set by Engauge or HART
SmartView for a specific functioning of the FII-RTD module in an
instrument. The default values are available after initialization of the
non-volatile memory; so check each entity for its correctness.
Explanation
4 Thresholds for activating a related
alarm status in the Primary Value
Enables (if activated, see next listed
entity) the simulation of one of the 4
alarms for a minute, by simulating the
actual measured Primary Value is
below or above the alarm threshold.
Activates and selects at the same time
the Alarm test (if enabled with the
[Alarm test enable]
listed before, and the
4 alarm thresholds are
properly set).
The name of the current function of
this module. This name is visible on
the HART SmartView.
Commissioning Check
After having checked/set all before listed entities, make sure
the [Board Commissioned], the [Product temperature
Commissioned], the [Vapour temperature Commissioned],
and the [Ambient Temperature Commis- sioned] entities
are <True>;
the [Board Health], the [Product temperature Health], the
[Vapour temperature Health], and the [Ambient Temperature
Health] entities are <GOOD>.
For viewing the software version, the Engauge Generic tab can be
viewed; also a Reset board command can be issued here.
NOTE: In the HART SmartView situation, the Commissioning flag
must be 'G' and the Health flag must be 'Y'.
Service Manual
954 SmartServo FlexLine
Value Range
floating point numbers:
<-x.x .. +x.x>
<enable>
<disable>
[No Alarm]
[High High
alarm] [High
Alarm]
[Low Alarm]
[Low Low alarm]
13 characters
Default
<+1.0E22>
<disable>
<No Alarm>
<Ambient temp.>
147