COMMISSIONING
7.3.4.14 Compensation
Name
[Setpoint compensation]
[Compensation wire
weight]
[Compensation
unbalance]
[Compensation density]
[Level compensation]
Part No.: 4417340 Revision 1
Value Range
<enable>
<disable>
<enable>
<disable>
Service Manual
954 SmartServo FlexLine
Default Value
Explanation
<enable>
Enable or disable the
following
<disable>
compensations for the
set point:
<disable>
-Wire weight
Compensates for the
wire weight
-Unbalance
Compensates for the
unbalance of the drum
and bearings
-Density
Compensates for the
change in density over
time
Shows the wire weight
compensation.
Shows the unbalance
compensation.
Shows the density
compensation.
<enable>
Enable or disable the
following
<enable>
compensations for the
<disable>
level:
-Magnet coupling
<disable>
Compensates level for
<disable>
the slip in the magnet
<disable>
coupling caused by
different weights
<disable>
-Magnet coupling
<disable>
temperature
Compensates level for
the slip in the magnet
coupling caused by
temperature
Note: Only applied
when Magnet coupling
compensation also is
enabled.
Note: Both magnet
couplings should be
(default) enabled
85