TROUBLE SHOOTING

Warnings

Status code
(SmartView)
6273
6274
6275
6276
6277
6278
6279
6280
6283
6285
6286
6287
6288
6289
6290
6291
286
Numbers in the range 6272-6335 are warning codes. Warnings will set
the status of the Primary value to UNCERTAIN.
Description
(Engauge)
No valid product level for
compensation
No valid temperature for tank shell
compensation
Balance test number of valid test
points too low
Balance test number of valid test
points too high
No valid vapour temp. for wire
temp. compensation
No valid magnet temp. for magnet
temp. compensation
No valid product level for
hydrostatic deformation comp.
No valid displacer temp. for
volume compensation
No valid product level or magnet
temp. for drum temp.
compensation
RIC configuration parameters not
commissioned
Product level below RIC minimum
level
Error getting HART dynamic
variables entity device address 11
Error getting HART dynamic
variables entity device address 12
Error getting HART dynamic
variables entity device address 13
Wrong HART units device address
11
Wrong HART units device address
12
Service Manual
954 SmartServo FlexLine
Remarks
E.g. because the displacer is not
measuring product level. Please check
the Primary value of the Product level.
One of the temperatures needed for
the tank shell compensation is not
available (refer to section 7.7.2.3).
Please check the vapour and product
temperatures on the FCI-HRT or
FII-RTD.
The unbalance table has too few valid
entries. Can appear when the
unbalance compensation for set point
or density is enabled. Perform a
balance test to provide a new table
(refer to sections
7.7.1
The unbalance table has too many
valid entries. Can appear when the
unbalance compensation for set point
or density is enabled. Perform a
balance test to provide a new table.
(refer to sections
7.7.1
Please check the vapour temperature
on the FCI-HRT.
Please check the magnet temperature
status (Board Specific).
E.g. because the displacer is not
measuring product level. Please check
the Primary value of the Product level.
Please check the product temperature
on the FCI-HRT.
Please check the magnet temperature
status (Board Specific) or the Primary
value of the Product level.
RIC warning
RIC warning
RIC warning
RIC warning
RIC warning
Part No.: 4417340 Revision 1
and 9.3.1).
and 9.3.1)