COMMISSIONING
7.3.7.3.2
Table 7-3
Table 7-4
Part No.: 4417340 Revision 1

P1 Pressure

The FCI-HT software only accepts the Primary Value of a P1 pressure
HART device in SI units kilo Pascals (kPa).
Make sure the P1 pressure HART device is configured to output data
in kilo Pascals (kPa). If not, correctly configure as yet, by using an
appropriate HART configuration tool.
Accepted HART
Sensor Type
P1 Pressure
Kilo Pascal

Accepted PV unit for a P1 HART device

NOTE: The Secondary and Tertiary values of a P1 pressure HART
device may be any units.
The PV of the P1 pressure HART device is read and converted into SI
Units Pascals (Pa) within the FlexConn function PV.
The value is filtered, and the filtering factor depends on the value set in
the entity
[P1 Integration
lower value gives less filtering.
The correction factor stored in the
from the filtered value. If the
Depending on the
displayed as either absolute pressure or relative pressure.
PV Unit Type
P1 Pressure

P1 pressure displayed unit types

If Relative pressure is selected, the value stored in the
Pressure]
entity is added to the measured pressure. If Absolute pressure
is selected, no factor is added. The final result is available in the
Value]
entity.
NOTE: Absolute pressure is used in the density calculation; the relative
pressure is only displayed in P1
Service Manual
954 SmartServo FlexLine
Abbreviation
PV Unit
kPa
time]. A higher value gives more filtering, and a
[P1 PV offset]
[P1 PV offset]
entity = 0 no offset is applied.
[PV selected type]
entity, the P1 pressure can be
Display Unit Type
Absolute
Relative
[Primary
Value].
HART PV Unit
Code
12
entity is then subtracted
PV selected type
1
2
[Ambient Air
[Primary
115