Hcm-Gpu Slave; Gpu Interface Address - Honeywell FlexLine SmartServo 954 Service Manual

Servo-based level gauge
Hide thumbs Also See for FlexLine SmartServo 954:
Table of Contents

Advertisement

COMMISSIONING
Figure 7-30
168
This setting is used for host systems that cannot switch directly from
sending to receiving. The delay time can be set between 0 and 2000
msec.
On the TAB sheet GPU-slave communication parameters can be set
such as: GPU and FlexConn interface addresses, parity and modem
control type (Refer to Figure "HCM-GPU Slave").

HCM-GPU Slave

Identification:
An 8 character long name for the HCM-GPU board.

GPU interface address:

The address of the SmartLink, ranging from 0 till 9 (similar as the CIU
address). Each SmartLink, connected to the same PC ComPort, must
have a unique address. If the GPU interface address is changed from
default, and the new address has been sent to the HCM-GPU module,
then also change the address at the SmartLink icon Properties TAB
sheet (one level higher).
Service Manual
954 SmartServo FlexLine
Part No.: 4417340 Revision 1