Advertisement

Step 8
Follow the figure below to ground the UPS, external battery cabinet(s) and connected critical
loads.
(Figure 5-20: Grounding Diagram_ Single Unit)
5.4.4.2 300kVA UPS Dual Input (Single Unit)
When there are two AC power sources, single unit wiring procedures are as follows.
Step 1
Follow 5.4.2 Single Input/ Dual Input Modification to modify the UPS from single input to
dual input.
Step 2
Follow Step 1 ~ Step 6 in 5.4.4.1 300kVA UPS Single Input (Single Unit).
Step 3
Connect the cables of the main AC source, bypass source, output and external battery
cabinet(s) to the UPS. Please refer to Table 5-3, 5.5 External Battery Cabinet Connection
Warnings and the following diagrams to perform wiring.