Delta Ultron Series User Manual page 149

Three phase 300-600 kva
Hide thumbs Also See for Ultron Series:
Table of Contents

Advertisement

Appendix 1 : Technical Specifications
Model
UPS Capacity
Nominal Voltage
Voltage Range
Input
Current Harmonic
Distortion
Power Factor
Frequency Range
Voltage
Voltage Harmonic
Distortion
Output
Frequency
Overload Capability
Display
Interface
Standard
Online Mode
Efficiency
ECO Mode
Nominal Voltage
Battery
Charge Voltage
300kVA/
400kVA/
300kW
400kW
220/380 Vac, 230/400 Vac, 240/415 Vac
(3Φ4W + G)
176 ~ 276 Vac*
40 ~ 70 Hz
220/380 Vac, 230/400 Vac, 240/415 Vac
(3Φ4W + G)
≤ 1.5% (linear load)
50/60 Hz
≤ 110%: 60 minutes*
≤ 125%: 10 minutes; ≤ 150%: 1 minute
10" Touch Panel
External battery temperature dry contact × 4,
External switch/ breaker status dry contact × 4,
Output dry contact × 6, Input dry contact × 4,
Parallel port × 4, USB type A × 2,
USB type B × 1, RS-232 port × 1,
MODBUS port × 1, BMS (RJ45) × 1,
Ethernet × 1, SMART slot × 1, REPO × 1
up to 96.50%
± 240 Vdc (Default)
± 272 Vdc (adjustable from 204 Vdc to 312 Vdc)
149
DPS
500kVA/
600kVA/
500kW
600kW
1
(full load)
2
≤ 3%*
> 0.99
3
;
99%