Delta Ultron Series User Manual page 130

Three phase 300-600 kva
Hide thumbs Also See for Ultron Series:
Table of Contents

Advertisement

Item
Restored Voltage
Charge Current (Max)
Auto Equalized
Charge
Auto Equalized
Charge Interval
Equalized Charge
Time
Battery Test Fail
Voltage
Battery Test Duration
Auto Battery Test
Interval
Low Temperature
Alarm
High Temperature
Alarm
Installation Date
Next Replacement
Date
Ultron DPS Series
Set up the restored voltage.
NOTE:
1. The item will only show up if the Battery Type is
set as 'LiB (Integration)'.
2. If the Battery Type is set as 'LiB (Dry Contact)',
the item will not show up.
Set up the maximum charge current.
Enable or disable the auto-equalized charge.
Set up the auto equalized charge interval.
Set up the equalized charge time.
Set up the battery test fail voltage. When the battery voltage is
under the test fail voltage, it means battery fail.
Set up how long the battery test should last.
Set up the battery test interval.
Enable or disable the low temperature alarm. If enabled, set
up the temperature.
Enable or disable the high temperature alarm. If enabled, set
up the temperature.
Record the battery installation date.
Set up the battery replacement date.