Delta Ultron Series User Manual page 143

Three phase 300-600 kva
Hide thumbs Also See for Ultron Series:
Table of Contents

Advertisement

Item
Sub Item
ID
Title
SENSOR
Status
Temperature
Humidity
Input Contact 1
Input Contact 2
INPUT
CONTACT
Input Contact 3
Input Contact 4
Set the ID # (ID 0/ ID 1/ .../ ID 15) according to the ID DIP
switch setting of the EMS 1000 (EnviroProbe) device.
NOTE:
If the ID # setting is wrong, the warning message
'The EMS 1000 ID # Communication Fail' will
appear.
Set the title for the EMS 1000 (EnviroProbe), 16 characters
at most.
The status 'Enable/ Disable' determines whether or not
the LCD shows the EMS information of the EMS 1000
(EnviroProbe) device (ID #).
Set the temperature (°C) values for Alarm/ Warning/
Recovery.
Set the Humidity (%) values for Alarm/ Warning/ Recovery.
1.
Set the input contact as Normally Open (NO)/
Normally Closed (NC).
2.
Set the Title for the input contact, 16 characters at
most.
3.
Set the Event Type as None/ Information/ Warning/
Alarm.
143