Delta Ultron Series User Manual page 150

Three phase 300-600 kva
Hide thumbs Also See for Ultron Series:
Table of Contents

Advertisement

Model
UPS Capacity
Protection of Battery
Deep Discharge
Operating Altitude
Operating
Temperature
Relative Humidity
Environment
Audible Noise
IP Degree of
Protection
Parallel
Redundancy
Emergency
Others
Power Off
Battery-start
Dimensions
(W × D × H)
Physical
Weight
Ultron DPS Series
300kVA/
400kVA/
300kW
400kW
1000 meters (without derating)
3280 ft (without derating)
0 ~ 40°C (32 ~ 104°F)
95% (non-condensing)
< 80 dBA*
1 meter (3.28 ft) in front of the UPS
Yes (up to 8 units)
600 ×
900 ×
2000 mm
23.6" ×
35.4" ×
78.7"
515 kg
700 kg
1135 lb
1543 lb
150
DPS
500kVA/
500kW
Yes
4
IP 20
Yes
Yes
1200 × 900 × 2000 mm
47.2" × 35.4" × 78.7"
811 kg
1787 lb
600kVA/
600kW
970 kg
2138 lb

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents