Connecting the Optional EMS 1000 (EnviroProbe)
1. You can connect a maximum of 16 optional EMS 1000 (EnviroProbe) devices to each
UPS to expand the environment monitoring range. A maximum of 8 UPS units can be
paralleled. Please use a CAT-5 cable (user-supplied & the cable length depends on the
on-site application and environment) to connect the EMS 1000 (EnviroProbe) to the EMS
port on the UPS. For the location of the EMS port, please refer to 4.2 Communication
Interfaces II: at the Rear of the Touch Panel.
2. The UPS only supports RS485 communication. When installing the EMS 1000
(EnviroProbe), please set the device's communication mode as RS485 following 3-1
Comm DIP Switch Settings of the EnviroProbe 1000 Quick Guide.
3. When installing the EMS 1000 (EnviroProbe), please set the ID # by the four ID DIP
switches on the left of the device following 3-2 ID DIP Switch Settings of the
EnviroProbe 1000 Quick Guide.
NOTE:
1. The ID # of each EMS 1000 (EnviroProbe) device connected to the UPS must
be different so that the UPS can identify each device.
Color
(Status)
The color represents the status of Temperature/
Humidity based on the EMS settings.
When the detected Temperature/ Humidity
1. is lower than the value set for Warning, it
shows Green (Normal).
2. is higher than the value set for Warning but
lower than the value set for Alarm, it shows
Yellow (Warning).
3. is higher than the value set for Alarm, it
shows Red (Alarm).
4. has reached the value set for Alarm/
Warning, the status will recover from Alarm
to Warning/ from Warning to Normal
respectively only when the detected value has
been lowered to its corresponding Recovery
value.
1. Different colors represent different status that
the input contact has detected.
2. The Title, NO/ NC, and Event Type of the
input contact can be adjusted according to
your needs.