Features

The CC–S
has the following characteristics:
0
q
Transmission speed for optical asynchronous input max. 2 x 19.2 kbaud (FO/LWL1 and
FO/LWL2).
q
The connection is automatically established after interruption of the ISDN connection or
shut down of the supply voltage.
q
The parameter assignment is done via the serial PC–Interface and the configuration
program FOS0–Configurator, which can be downloaded from
download_neu/ind_acc_e.htm. Alternative a simple Terminal Program, e.g. Hyper Termi-
nal, can also be used.
q
Connections to the protection device via a noise proofed fibre optic cable to a FO module
integrated there.
q
Maximum fibre optic cable length for the connection between protection device ↔
CC–S
1.5 km (1 mile) with 62.5/125 µm multi–mode fibres. Connection with
0
ST–connector.
q
A 5-pole screw terminal is used for the data connection between the communication
device (DCE, NTBA) and CC–S
q
Maximum line length for the connection between communication device (DCE, NTBA) ↔
CC–S
150 m (450 ft).
0
q
A 9 pole SUB–D connector for the parameter assignment interface (RS232; PC–Inter-
face)
q
Power supply unit with extended range for direct voltage 24 VDC to 250 VDC (limit
voltage 19 VDC to 300 VDC) and alternating voltage 115 VAC to 250 VAC (range
92 VAC to 286 VAC).
q
Monitoring the auxiliary voltage, the clock signal of the communication network and the
internal logic.
q
Rigid aluminium die–cast housing with the dimensions 188 mm × 120 mm × 56 mm
(W × D × H) for DIN rail mounting.
q
Signalling the operating states via LED.
q
Power consumption < 3.5 VA.