Siemens 7XV5662-0AB01 Directions For Use Manual page 60

Communication converter s0-bus with optical asynchronous input interface
Table of Contents

Advertisement

Available languages

Available languages

English
Ones you have entered the configuration mode, the parameter of the CC–S
assigned by some commands (see table 12).
Command
show
save
reset
defa 1
isdn x
aciomco n
aciomcatab1
aciomcatab2
vmoddi/1.msni
vmoddi/2.msni
Table 12: Terminal commands
60
Description
shows the actual parameter assignment of the CC–S
terminal
saves the parameter into a resident memory
resets the CC–S
0
resets all parameters to the state as delivered
assigns the D–Channel–Protocol:
x=0 dialling line (DSS1)
x=12 leased line for channel B1
x=13 leased line for channel B2
x=14 leased line for channel B1 and B2
assigns how many B–Channel has to be established and which
numbers are dialled after Reset or Power On:
n=0 both B–Channels are established, the dialled numbers
are the number assigned at aciomcatab1 and
aciomcatab2
n=1 only channel B is established, the dialled number is the
number which is assigned at aciomcatab1
n=2 only channel B is established, the dialled number is the
number which is assigned at aciomcatab2
n=3 no B–Channel is established
assigns the dialling number for FO1/LWL1 after Reset or
Power On
assigns the dialling number for FO2/LWL2 after Reset or
Power On
assigns the number which is routed through the FO1/LWL1–
Connection by an incoming call.
assigns the number which is routed through the FO2/LWL2–
Connection by an incoming call
can be
0
on
0
C53000-B1174-C166-1