Figure 36 Screen shot terminal program
In the table 14 all parameters are listed and described to assign the CC–S
Command
defa 1
aciomco 1
aciomcatab1
04012345
aciomcatab2
091167890
isdn 0
vmoddi/1.msni
03012345
vmoddi/2.msni
03067890
save
show
reset
Table 14: Parameter assignment of the CC–S
62
Description
resets all parameter to the state of delivery
only one B–Channel starts dialling after Reset/Power On or an
interruption of the communication. The dialled number is
04012345 (assigned at aciomcatab1)
04012345 is the dialled number for FO1/LWL1
091167890 is the dialled number for FO2/LWL2
sets the ISDN–Protocol to DSS1 (Dialling Line)
If the an incoming call had dialled 03012345 the data are
routed through FO1/LWL1
If the an incoming call had dialled 03067890 the data are
routed through FO2/LWL2
save the assigned parameters into a resident memory
show the actual parameters of the CC–S
restarts the CC–S
0
with the new assigned parameters
#1 (Berlin)
0
#1 (Berlin):
0
(see figure 37)
0
C53000-B1174-C166-1