Function
Default
Alarm cancel
006 minutes
RF time-out
12 hours
Fail-to-open time
Off
Fail-to-close time
Off
Siren time-out
005 minutes
Arm LED shutdown Off
Unvacated
On
premises
Smoke supervision
Off
46
Description
Sets the time frame that determines whether the panel
reports an alarm cancel message to the central station. If
the system is disarmed from an alarm state within the
programmed time, the panel sends an alarm cancel
message to the central station. An alarm cancel message is
not reported if the system is disarmed after the programmed
time expires.
The time can be set from 006 to 255 minutes. When set to
255, the panel always reports alarm cancel messages.
Turning off this option disables alarm cancel reporting.
Determines the period during which the panel must receive
at least one supervisory signal from learned sensors before
identifying a sensor failure and sounding trouble beeps. Any
sensor failure is reported immediately and again at the
supervisory time. The timeout can be set from 02 to 36
hours. Entries must be two digits.
Determines whether the panel sends a fail-to-open report to
a central station if the system has not been disarmed by the
programmed time (on), or not (off). System time must be set
correctly for this feature to work.
Determines whether the panel sends a fail-to-close report to
a central station if the system has not been armed by the
programmed time (on), or not (off). System time must be set
correctly for this feature to work.
Determines how long sirens sound alarms if no one is
present to disarm the system. The time can be set from 002
to 254 minutes. When this feature is turned off, sirens
sound alarms until the alarm is canceled (system disarmed).
Determines whether the panels LEDs (buttons) turn off 30
seconds after the last button press (on), or remain on for the
entire arming period (off).
Determines whether the system automatically arms down to
level 2 (doors and windows) if you arm the system to level 4
(doors, windows, and motion sensors) without leaving the
premises (on), or remains at the armed level chosen (off).
This feature does not work from a key fob. Autobypass must
be on for this feature to work.
Determines how often the panel must receive supervisory
signals from the smoke sensors. If this option is on, the
panel must receive at least one supervisory signal from
smoke sensors every four hours or it will identify a sensor
failure and sound trouble beeps. If this option is off, the time
for receiving supervisory signals is determined by RF
timeout.
Simon XT Installation Manual