4.10.3

Control unit CC1142

Existing localization
data in RAM are
erased during a
download!
RS232 interface: plug
ST2 on E3X10x
Fire & Security Products
Siemens Building Technologies Group
Procedure
Connect the serial interface of the maintenance PC (COM1) and the CC11 control unit
(connector ST2 on E3X10x) via the modem box Z3W050/51 + adapter box B3D040 or
via the modem box B3D021
Start the SWE11
Load the CC11 control unit configuration data
Õ Ensure C-Bus address is correct!
Start transfer of configuration data from the SWE11 to the CC11 control unit
Õ Function Comm. Õ Fast Download –> CS11 (only with modem box B3D021) or
Õ Function Comm. Õ Download CS11
If there is not enough available memory (RAM) on the control unit, the message 'No
database memory available' appears on the SWE11 information line. In such cases,
refer to page 81.
After a successful download the following message appears in the SWE11: 'Operation
successful'
Once the startup procedure on the control unit has been completed, the green LED on
the E3X10x starts to flash regularly: Lit phase is as long as the unlit phase ( approxi-
mate period length: 1 second)
É
É
Adapter B3D040 + Z3W050/51
or
modem box B3D021
CC11
Serial interface
É É É É
(COM1)
Loaded CC11 con-
trol unit configura-
tion data
SWE11
73
e1249d 3
01.1999