Siemens Cerberus CS1140 Commissioning page 54

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

Input module DC1131/DC1131-AA
select
AlgoWorks 00ST0245
File: C:\AWDATA\DEMO_VPB\DCR001L1.TXT
Listing of the logical structure (26447,19533,31046)
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
001/AR/demo system VPB
(1801,1)
001.001/SE fire/2nd floor west
001.001.001/ZO single/1/laboratory 201
>001.001.001.001/001: DO1131
4
>001.001.001.002/001: DO1131
2 AI
>001.001.001.003/001: DO1131
>001.001.001.004/001: DO1131
001.001.002/ZO multi/2/laboratory 203
>001.001.002.001/004: DOT1131
6 Window
>001.001.002.002/004: DOT1131
5 Door
Output module DC1134/DC1134-AA
select
AlgoWorks 00ST0245
09–APR–1997, 14:42
File: C:\AWDATA\DEMO_VPB\DCR001L1.TXT
Listing of the logical structure (26447,19533,31046)
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
001/AR/demo system VPB
(1801,1)
001.001/SE fire/2nd floor west
001.001.001/ZO single/1/laboratory 201
>001.001.001.001/001: DO1131
4
>001.001.001.002/001: DO1131
2 AI
>001.001.001.003/001: DO1131
>001.001.001.004/001: DO1131
001.001.002/ZO multi/2/laboratory 203
>001.001.002.001/004: DOT1131
6 Window
>001.001.002.002/004: DOT1131
5 Door
50
Fire & Security Products
Siemens Building Technologies Group
Procedure
1. Switch over from the physical structure to the localization structure
Õ Function Loc. Õ Commissioning
2. Using the commissioning list, select a DC1131 input module in the localization struc-
ture and the corresponding element in the logical structure
Permissible element types:
– 'Digital element' ('EL digital')
– 'Digital detector element' ('EL digital det.')
– 'Digital manual call point element' ('EL digital man.')
– 'Command element' ('EL command')
– 'Output element with confirmation' ('EL out 2') Õ as confirmation path only
ý 'EL out 2' Ý see 'Restriction' page 49
Reference:
Localization index of the address allocation
09–APR–1997, 14:42
(1701,425)
(1601,426)
(1501,427)
(1501,428)
(1501,429)
(1501,430)
(1602,445)
(1501,446)
(1501,447)
3. Link nodes together
Õ Function Structure Õ Link
Procedure
1. Switch over from the physical structure to the localization structure
Õ Function Loc. Õ Commissioning
2. Using the commissioning list, select a DC1134 output module in the localization
structure and the corresponding element in the logical structure
Permissible element types:
– Output element without confirmation ('EL out 1')
– Output element with confirmation ('EL out 2') Õ as output path only
ý 'EL out 2' Ý see 'Restriction' page 49
– Remote transmission channel element ("EL RT ch")
Reference:
Localization index of the address allocation
(1701,425)
(1601,426)
(1501,427)
(1501,428)
(1501,429)
(1501,430)
(1602,445)
(1501,446)
(1501,447)
3. Link nodes together
Õ Function Structure Õ Link
e1249d 2