Commissioning Overview - Siemens Cerberus CS1140 Commissioning

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

2

Commissioning overview

Requirements . Page 3
– Control unit installed and peripheral equipment is connected
– All necessary hardware is available
Requirements
Compact control unit CI1145 . Document e1577
– Installation and connection of hardware
Control unit CC/CI1142 . Page 4 ff
– Install power unit
– Connect mains cable and feed line
Carry out the following operations as per system documentation:
– Mount module chassis and attach connection cable
– Set I-Bus addresses in all modules / Set switches and jumpers
– Insert RAM modules and EPROMs in E3Xxxx or B3Qxxx and possibly E3Hxxx
– Connect all modules
– Connect I-Bus flat cables and supply cables to all modules
– Connect batteries
– Connect fire control installations
Terminal CT11 . Page 17
– Insert labels
– Remove protective cover and install RAM modules and EPROMs
– Connect C-Bus and supply as described in the system documentation
– Install terminal
First switch-on . Page 25
– Apply supply voltage
+ observe safety guidelines
– Start-up procedure
Þ Control unit is ready for device localization or data transfer from maintenance PC
Requirements . Page 26
– Locations of the devices (automatic detectors, input/output modules, manual call points) must
be specified
– Maintenance PC with installed AlgoWorks and system data files must be available
Localization or address assignment for the individual devices . Page 27 ff, 58 ff
– Enter device locations (interactive and AnalogPLUS devices) or assign bus addresses to the
detector bus according to the order of installation (AnalogPLUS and MS9i devices)
Allocations . Page 38 ff
– Upload the localization structure from the CC/CI11 control unit into the SWE11 and allocate
localization data to the associated logic elements (only possible after localization)
Download the configuration data . Page 68 ff
– Load system data from the SWE11 into the various stations (CC/CI/CT11)
– Start up and test the system
2
Fire & Security Products
Siemens Building Technologies Group
e1249d 1
01.1999

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents