First Switch-On - Siemens Cerberus CS1140 Commissioning

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

3.6

First switch-on

Fire & Security Products
Siemens Building Technologies Group
Check whether the batteries are connected.
Apply supply voltage à Observe safety guidelines
. the CC/CI/CT11 stations load a basic configuration stored in EPROM into the RAM.
After approx. 2 minutes this start-up procedure is concluded.
Master Module E3X101 (E3X100)
Green LED on CPU module
Õ irregular flashing: lit phase clearly shorter than the unlit phase (approximate period
length: 1 second)
Green battery indicator LED
Control unit CI11 or Terminal CT11 (B3Qxxx)
LCD display gives the following INFORMATION:
INFORMATION
******** load data ********
select MESSAGE CATEGORY
. CT11 and CC/CI11 only communicate with each other after the system configuration
has been loaded into the stations.
. Control unit is ready for the localization of interactive or AnalogPLUS devices or data
transfer from the maintenance PC.
flashes (Õ see page 24)
3
Lights up(Õ see page 24)
4