Siemens Cerberus CS1140 Commissioning page 48

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

Correct:
Zone
'EL out 2'
DC1154
No.1
in
'DE DS11i'
'FU DS11i'
Station
DC1154 Õ is repre-
sented in the physical
structure by 2 individual
devices (out / in)
'DE DS11i out'
44
Fire & Security Products
Siemens Building Technologies Group
Logical
structure
Links
out
Physical
structure
Procedure to be adopted if the input section and output section are used sepa-
rately
ü
The two physical devices are linked to two different logical elements
ü
Types of element to be used for the output section:
– Output element without confirmation ('EL out 1') or
– Element remote transmission channel ('EL RT ch.')
and for the input section:
– Digital element ('EL digital') or
– Digital detector element ('EL digital det.') or
– Digital manual call point element ('EL digital man.') or
– Command element ('EL command')
Zone
Zone
'EL out 1'
'DE DS11i in'
'FU DS11i'
Station
S
1. Switch over from the physical structure to the localization structure
Õ Function Loc. Õ Commissioning
2. Using the commissioning list, select a DC1154 output module in the localization
structure and the first of the corresponding elements in the logical structure, e.g. the
'output element without confirmation' ('EL out 1') linked to the output section
Incorrect:
'EL out 2'
DC1154
No.1
in
Logical
e.g. 'EL digital
structure
det.'
Links
Physical
structure
Zone
Zone
out
in
'FU DS11i'
Station
Station
Function unit
'150: DC1154'
DC1154 Õ is represented
in the localization structure
by one device
'EL out 1'
DC1154 No.
2
out
'DE DS11i'
Localization
structure
e1249d 2
01.1999