Siemens Cerberus CS1140 Commissioning page 59

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

Correct:
Zone
'EL out 2'
DC1136
No.1
in
'DE DS11a'
'FU DS11a'
Station
DC1136 Õ is repre-
sented in the physical
structure by 2 individual
devices (out / in)
Fire & Security Products
Siemens Building Technologies Group
Procedure
1. Switch over from the physical structure to the localization structure
Õ Function Loc. Õ Commissioning
2. Using the commissioning list, select the 'DC1136o' output section from a DC1136
output module in the localization structure and the corresponding 'output element
with confirmation' ('EL out 2') in the logical structure
Reference:
Localization index of the address allocation
3. Link nodes together
Õ Function Structure Õ Link
4. Select the corresponding 'DC1136i' confirmation section in the localization structure
(always a D-Bus address higher than the equivalent output section) and the same
'output element with confirmation' ('EL out 2')
5. Link nodes together
Õ Function Structure Õ Link
CAUTION: The two devices linked with the element 'EL out 2' must belong to the same
DC1136 i.e. the input of a DC1136 may only be used as confirmation path to the output of
the same DC1136!
Logical
structure
Links
out
'DE DS11o'
Physical
structure
DC1136 as output element without confirmation
Use only in exceptional circumstances!
ü
Element type to be used: 'Output element without confirmation' ('EL out 1')
e.g. 'EL out 1'
'DE DS11a in'
Incorrect:
Zone
'EL out 2'
DC1136
No.1
in
out
'FU DS11a'
Zone
'DE DS11a out'
Function unit
Station
Zone
'EL out 1'
DC1136
No.2
in
out
Station
Logical
structure
Links
Physical
structure
55
e1249d 2
01.1999