4.3

Localization of interactive devices

4.3.1

Overview of localization methods

Localization by address allocation
Activate localization mode
Address allocation by
insertion
Insert detectors in any or-
der (activate fixed devices)
and note order in commis-
sioning list / ground plan,
or register the inserted /
activated devices in the
SmartHandy
Deactivate localization mode,
upload localization data from the control
unit into the SWE11
Using the SWE11 allocate the devices of the localization structure to the
corresponding elements of the logical structure; use SmartHandy or Algo-
4.3.2

Address allocation through insertion

Requirements
Switch control unit to 'Address allocation through insertion' mode
Fire & Security Products
Siemens Building Technologies Group
Address allocation by
activation
Activate devices in any or-
der and note the order in
the commissioning list /
ground plan or register the
activated devices in the
SmartHandy
Man data where possible
Automatic detectors:
Detector base mounted
Detectors not yet inserted
Fixed devices (manual call points, input/output modules):
Terminal block mounted
Electronics inserted
ÕFixed devices are also localized in 'Localization through insertion' mode by
'Activation'.
Wait until the control unit is ready
Localization by means of device identification
Write down the printed detector identification numbers in
any order and note the order in the commissioning list /
ground plan. After registration of ID numbers insert de-
tectors in the bases or register with AlgoMan
Additional devices are
localized using address al-
location
The data of the detectors
localized using the device
ID are automatically read in
during address allocation
and loaded into the SWE11
during data transfer
All detectors are localized
using ID numbers
Activate localization
mode Õ the detector
data is read by the con-
trol unit
Deactivate localization
mode,
upload localization data
from the control unit to
the SWE11
(Õ page 91)
e1249d 2