Enter localization index in the commissioning list / ground plan or register in
the SmartHandy
AlgoWorks 00ST0245
File: C:\AWDATA\DEMO_VPB\DCR001L1.TXT
Listing of the logical structure (26447,19533,31046)
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
001/AR/demo system VPB
001.001/SE fire/2nd floor west
001.001.001/ZO single/1/laboratory 203
>001.001.001.001/001: DOT1131
>001.001.001.002/001: DOT1131
>001.001.001.003/001: DOT1131
>001.001.001.004/001: DOT1131
001.001.002/ZO multi/2/laboratory 201
>001.001.002.001/004: DO1131
>001.001.002.002/004: DO1131
laboratory 201
2
laboratory 203
1
laboratory 205
Repeat the procedure until all required devices have been localized
Deactivate address allocation
4.5

Allocations

4.5.1

Interactive and AnalogPLUS devices (after localization)

38
Fire & Security Products
Siemens Building Technologies Group
09–APR–1997, 14:42
(1801,1)
(1701,425)
(1601,426)
2
(1501,427)
3
AI
(1501,428)
1
(1501,429)
(1501,430)
(1602,445)
Window
5
(1501,446)
4
Door
(1501,447)
office
office
office
5
8
202
204
206
4
3
corridor 200
10
9
7
office
office
office
6
207
209
211
Devices, lines, and inputs/outputs of the physical structure are linked with the corre-
sponding elements of the logical structure using the SWE11. In the case of interactive and
AnalogPLUS devices, the localization data (bus address and, in the case of interactive
devices, the ID number) are also allocated.
Principle
Building layouts/logical connections (logical structure) and hardware configuration
(physical structure) are produced by the SWE11. The lowest levels of both of these struc-
tures – logical elements and physical devices – are linked to one another.
During address allocation, the location data on the CC/CI11 main control unit are also
registered in the form of a tree structure. This structure corresponds to the physical ar-
rangement of the installed hardware, but contains only the data necessary for location,
i.e.: bus addresses, ID numbers (interactive devices only), device models, address al-
location localization indexes.
Using the SWE11, the localization structure data must be assigned to the devices of the
physical structure/elements of the logical structure that have already been linked. The
reference for assignment is the address allocation localization index or the device ID (in-
teractive devices only).
2nd floor west
laboratory 201
001: DO1131
or
002: DO1131
003: DO1131
004: DO1131
(Functional characteristics of the
SmartHandy see document e1689)
(Õ page 93)