Automatic allocation of devices using the function 'Auto link'

Fire & Security Products
Siemens Building Technologies Group
The CC/CI11 station and all function units present are automatically localized provided
that the bus addresses, models and line numbers (AnalogPLUS line modules only) pro-
grammed in the physical structure match the actual settings.
Logical
structure
Links
I-Bus 2
I-Bus 1
C-Bus 1
Physical
structure
Principle
With the manual procedure each device of the localization structure is individually allo-
cated using the commissioning list / ground plan for the corresponding element of the log-
ical structure. The function Auto link simplifies the allocation procedure by automatically
linking the localization data with the localization indexes assigned to the logical structure.
The localization indexes are in turn either allocated by reading in the SmartHandy data
(for description see document 1689) or – as adopted in the following sections – by
manual transfer of the localization indexes from the commissioning list / ground plan.
This is done by means of Loc. Õ Set loc. index.
Allocations
I-Bus 1
Localization
structure
(Õ page 94)
(Õ page 98)
(Õ page 100)
– Device type
– Bus address
– ID numbers
– Location index
I-Bus 2
C-Bus 1
Location data
Devices
Function units
Station
39
e1249d 2
01.1999

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents