7.4

Tips for localization

7.4.1

Commissioning list for address allocation

Õ SWE11 printout of the logical structure:
AlgoWorks 00ST0251
File: C:\AWDATA\DEMO_VPB\DCR001L1.TXT
Listing of the logical structure (26447,19533,31046)
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
001/AR/demo system VPB
001.001/SE fire/2nd floor west
001.001.001/ZO single/1/laboratory 201
>001.001.001.001/001: DO1151
>001.001.001.002/001: DO1151
>001.001.001.003/001: DO1151
>001.001.001.004/001: DO1151
001.001.002/ZO multi/2/laboratory 203
>001.001.002.001/004: DOT1151
>001.001.002.002/004: DOT1151
7.4.2

Commissioning list for device identification

Õ Hand-written list:
01: demo system VPB
Area:
01: 2nd floor west
Section:
Location
laboratory 201 window left
laboratory 201 window right
laboratory 201 door left
laboratory 201 door right
laboratory 203 window left
laboratory 203 window right
laboratory 203 door left
laboratory 203 door right
7.4.3

Ground plan for address allocation or device identification

Õ Ground plan (building owner):
5
laboratory 201
4
2
3
laboratory 203
1
80384790
laboratory 205
96
Fire & Security Products
Siemens Building Technologies Group
(1801,1)
4
AI
5
1
window
3
door
Detector
type
DO1151
DO1151
DO1151
DO1151
DOT1151
DOT1151
DOT1151
DOT1151
office
office
office
8
202
204
206
corridor 200
10
9
7
office
office
office
6
207
209
211
Note down the localization index next to
the relevant element on the SWE11 print-
09–APR–1997, 14:42
out of the logical structure
Special description, showing to which
elements external response indicators
(AI) are connected
(1701,425)
(1601,426)
It can be useful to record the exact places
(1501,427)
of installation of individual elements for
(1501,428)
zones with more than one element, e.g.
(1501,429)
window, door, ...
(1501,430)
(1602,445)
Notes: If the input/output components of
(1501,446)
a DC1154 are used separately → note
(1501,447)
the localization indexes of both ele-
ments!
If more than one input of a DC1157 is
used → note the localization indexes of
all elements!
ID number
95683489
25897954
Enter detector ID number, detector type
34956746
and a unique description of the device
39064789
localization
80384790
89727568
21674374
36568852
Address allocation
Note down the localization index on the
ground plan next to the device concerned.
Localization by means of device identifica-
tion
Note down the ID number on the ground
plan next to the device concerned.