Page 1
Infrared Flame Detectors QRI... Infrared flame detectors for use with Siemens burner controls, for the supervision of gas, oil and other flames that emit infrared light. The QRI... are suited for burners of any capacity, either in continuous or intermittent operation.
Warning notes To avoid injury to persons, damage to property or the environment, the following warning notes must be observed! Do not open, interfere with or modify the flame detector! · All activities (mounting, installation and service work etc.) must be performed by qualified staff.
Installation notes Locate the detector such that, if possible, only the flickering peripheral range of the flame will be detected. The view at hot boiler walls or other hot boiler or burner components must be restricted as much as possible. This can be attained by clearly confined viewing conditions behind narrow baffle plates.
Page 4
ISO 14001:2015 OHSAS 18001:2007 China RoHS Hazardous substances table: http://www.siemens.com/download?A6V10883536 For use in the U.S. / Canada, the flame detectors carry the marks. Service notes To clean the detector’s lens, use a soft, clean cloth (free from oil and solvents).
Page 6
Technical data General detector data Operating voltage Operation DC 14 V ±5% Test DC 21 V ±5% Signal voltage DC 0...5 V Length of connecting cable Max. 180 cm Degree of protection IP54 Power consumption <0.5 W Length of auxiliary detector cable Max.
Page 7
Maximum detector If the connecting cable length of 180 cm is not sufficient, the burner manufacturer can cable length extend it up to a maximum of 100 m (also see Installation notes). SIEMENS Landis & Staefa Made in Germany 7719m04/1199 max.
Page 8
Spectral curves Flames Relative intensity of radiation Wave length (µm) Spectral emission of radiation of luminous and nonluminous flames at 1,500 K (extract from VDI Report no. 423, 1981). Legend Black body radiation Pulverized coal flame Oil flame Gas flame Sensitivity of flame detector 100 %...
Page 9
Measuring circuit and connection examples Measurement of the See Signal voltage in Technical data. detector current LMV5... X10-02 / 6 X10-02 / 4 Made in Germany X10-02 / 2 7719a01/1213 0...10 V > 10 M Measurement of the detector’s signal with a Voltmeter is not normally required since the flame signal’s intensity is shown on the AZL5...
Page 10
Dimensions Dimensions in mm 144,5 QRI2B... for lateral illumination Made in Germany 7719m02/0603 QRI2B... viewing angle Infrared rays Legend Available cable length (see Type summary) 144,5 QRI2A... for frontal illumination 162,8 QRI2A... viewing angle Infrared rays Legend Available cable length (see Type summary) 10/12 Building Technologies CC1N7719en...
Page 11
Dimensions (cont’d) Cable ends stripped Connecting cable Brown Blue Black 7719m01e/0302 Mounting kit AGG2.110 Clamp (4 199 8806 0) + adapter sleeve + heat insulating piece 7719m11/1013 Adapter AGG2.120 SW24 28,5 11/12 Building Technologies CC1N7719en 17.07.2018...
Page 12
LN 3 8380 0102 0,2 mm elevated Flange with radius 4 241 88550 R0,3 7719m10e/0114 Company logo to LN 3 8380 0102 0,2 mm elevated ã2018 Siemens AG Building Technologies, Berliner Ring 23, D-76437 Rastatt Subject to change! 12/12 Building Technologies CC1N7719en 17.07.2018...