Switching On For The First Time - Siemens AlgoRex CS1140 Comissioning Hardware

Fire detection system
Hide thumbs Also See for AlgoRex CS1140:
Table of Contents

Advertisement

17

Switching on for the first time

Building Technologies
Fire Safety
1. Check whether the batteries are connected.
2. Establish mains voltage. Note 2 'Safety regulations' chapter.
The 'CC'/'CI'/'CT' stations load basic configuration stored in the EPROM into
the RAM. This start-up procedure is complete after around 2 minutes.
Control panel module E3X10., battery charging plug-in module E3C011
Green 'H1-2' LED on CPU part (1) flashing. Irregular flashing: Illuminated phase
κ
considerably shorter than dark phase (period lasts around 1 second).
Green 'H501-2' LED (2) 'Mains operation' lights up.
κ
H1-2
1
H501-2
2
Operating terminal B3Q... and/or 'CI' control panel
LCD contains the following 'NOTE' (information):
κ
INFORMATION
********load data********
'CT' and 'CC/CI' only communicate with one another once the system configura-
κ
tion has been loaded in the stations.
Control panel is ready to localize Sinteso
κ
AnalogPLUS devices or transfer data from the maintenance PC.
E3X10.
Total: 1
TM
devices, interactive and/or
Switching on for the first time
E3C011
H501-2
2
008726_e_en_--
39
06.2017