Disabling Switch-Off And Switch-On Messages; Delegating Multiple Alarms For 'Zones; Configuring Bacnet Client - Siemens FS720 Configuration

Fire detection system
Table of Contents

Advertisement

'Network' task card
14
Global BACnet configuration

14.7.2 Disabling switch-off and switch-on messages

14.7.3 Delegating multiple alarms for 'Zones'

14.7.4 Configuring BACnet client

332 | 412
Building Technologies
Fire Safety
In the standard setting, messages for switching logical channels off and on are
sent to connected ↑ BACnet clients. These messages can be disabled.
Figure 153: Global BACnet settings
Disable switch-off and switch-on messages as follows:
1. Highlight 'Global BACnet configuration'.
2. Select the 'Details' tab in the detail editor.
3. Check the 'Suppress BACnet mode 'OFF' in channels' checkbox.
a Switch-off and switch-on messages are disabled.
In the standard setting, the ↑ pre-alarm and alarm messages are signaled on the
'Zones'. This leads to problems in the ↑ BACnet model if it is in the 'Multiple alarms
per zone' setting.
Figure 154: Global BACnet settings
These BACnet messages can be delegated to the logical channels and replace the
messages for 'Activation' there.
Activate the 'Multiple alarms per zone on BACnet' as follows:
1. Highlight 'Global BACnet configuration'.
2. Select the 'Details' tab in the detail editor.
3. Check the 'Multiple alarms per zone on BACnet' checkbox.
a 'Multiple alarms per zone on BACnet' is activated.
The 'BACnet client configuration' element must be created in the tree view of the
'Network' task card so that the ↑ BACnet client can be configured.
This element defines the ↑ management stations or third-party devices that are
accepted by the FS720 system. The customer text of this element is also used in
the event memory to log all actions triggered by a management station.
A BACnet client is identified by the 'BACnet device ID'.
A6V10210424_j_en_--
2018-08-29