Siemens AlgoRex CS1140 Comissioning Hardware

Fire detection system
Hide thumbs Also See for AlgoRex CS1140:
Table of Contents

Advertisement

®
AlgoRex
CS1140
Fire detection system
Commissioning hardware
EP7F
Building Technologies
Control Products and Systems

Advertisement

Table of Contents
loading

Summary of Contents for Siemens AlgoRex CS1140

  • Page 1 ® AlgoRex CS1140 Fire detection system Commissioning hardware EP7F Building Technologies Control Products and Systems...
  • Page 2 Data and design subject to change without notice. / Supply subject to availability. © Siemens Switzerland Ltd 2005-2017 We reserve all rights in this document and in the subject thereof. By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part, nor to make them available to any third party without our prior express written authorization, nor to use it for any purpose other than for which it was delivered to him.
  • Page 3: Table Of Contents

    About this document ................5 Safety regulations ................7 Signal words and symbols ..............7 2.1.1 Classification and meaning of signal words ..........7 2.1.2 Symbols and their meaning ..............7 2.1.3 Classification and meaning of additional symbols ........8 Safety-relevant working instructions ............8 Commissioning overview ..............10 Commissioning the system ..............
  • Page 4 Operation and floor repeater display ..........27 11.1 B3Q... AlgoPilot operating terminal ............27 11.2 B3Q321 fire brigade operating unit ............27 11.3 B3R051 parallel display ............... 27 11.4 K3R072 mimic display board..............28 11.5 K3G060 relay board ................28 11.6 K3I050 LON/mimic display converter ...........
  • Page 5: About This Document

    About this document About this document Goal and purpose This document describes commissioning of the hardware components of control panel CS1140/45. Safe applications will result from consistently following these in- structions. Scope of validity This document contains information valid for software variant EP7F. Target audience This product documentation and the operating instructions are intended for the fol- lowing people, who carry out a particular job and have been trained for it.
  • Page 6 Products are designed for proper use, and before they are delivered they are test- ed to ensure they function correctly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or disregard of warn- ings of danger contained in the documentation.
  • Page 7: Safety Regulations

    Safety regulations Safety regulations This chapter describes the danger levels and the relevant safety regulations appli- cable for the use of our products. Please read the work instructions as well as the chapter 1 'About this document' before beginning any work. Signal words and symbols 2.1.1 Classification and meaning of signal words...
  • Page 8: Classification And Meaning Of Additional Symbols

    Safety regulations 2.1.3 Classification and meaning of additional symbols Tips and information. Refers to extremely important or critical decisions to be taken into account before continuing the work. Safety-relevant working instructions Country-specific standards The products are developed and produced in compliance with the relevant Euro- pean safety standards.
  • Page 9 Safety regulations Testing the product operability Evacuate and cordon off the extinguishing sector. κ Inform people about the possibility of fogging and noise. κ Inform people before testing alarm devices; take the possibility of panic reac- κ tions into account. Inform the alarm and fault receiving stations connected to the system before car- κ...
  • Page 10: Commissioning Overview

    Commissioning overview Commissioning overview Commissioning the system CI1145 CI1145 CT1142 CC1142 Precondition for complete work 1. Control panel fitted and detector lines ready for connection (1), or detector lines connected to separate connection panel (2). 2. Peripheral devices such as operating terminal (3), plain text operating terminal, parallel display, etc.
  • Page 11: Preparations

    Commissioning overview 3.1.1 Preparations Compact control panel CI1145 –> see document 008727 κ Fit and connect the hardware – Control panel CC/CI κ according to system documentation: Fit power supply unit – Connect mains cable and supply line – Fit board holder and attach connection cable –...
  • Page 12: Fitting The Hardware

    Fitting the hardware Fitting the hardware Fitting and connecting hardware CI1145 For a complete description of the installation process for the various variants of the CI1145 control panel –> see document 008727. Fitting board holder in CS1140 For details of installation instructions –> see reference documents in chapter 1 Item Component Preparation...
  • Page 13: Cpus

    CPUs CPUs E3X101 control panel module Take measures to protect against overvoltage when inserting RAM and NOTE EPROMs. Press modules all the way into the base. Item Component Preparation Default ex factory RAM kit (2x 512Kx8 bits) Z3S070 Insert in pos. 'D11' / 'D12' Not used 0 ς...
  • Page 14: E3X102/103 Control Panel Module

    CPUs E3X102/103 control panel module Item Component Preparation Default ex factory SRAM – E3X102 (2x512Kx8 bits) E3X103 (4x512Kx8 bits) Flash ROM – Program file E3X102 CCX00xxx E3X103 CCY00xxx 'S2' programming switch: Battery type Set to battery make used, see description in docu- 'ALARMCOM (FIAMM)' type selection ment 001260...
  • Page 15: B3Q460/480/485 Operating Terminal Can Be Used As 'Ct' Or 'Ci

    CPUs B3Q460/480/485 operating terminal can be used as 'CT' or 'CI' Take measures to protect against overvoltage when inserting RAM and NOTE EPROMs. Press modules all the way into the base. Item Component Preparation Default ex factory Shielding hood Remove (refit in last step) Fitted RAM kit (2x 512Kx8 bits) Z3S070 Insert in pos.
  • Page 16: B3Q66X/670/68X/56X Operating Terminal Used As 'Ct' Or 'Ci

    CPUs B3Q66x/670/68x/56x operating terminal used as 'CT' or 'CI' Item Component Preparation Default ex factory SRAM – B3Q6xx (2x512Kx8 bits) B3Q565 (4x512Kx8 bits) Flash ROM If using as 'CI', load other program file: Program file as 'CT' B3Q6xx CIX00xxx B3Q6xx CTX00xxx B3Q565 CIYTxxxx B3Q565 CTYTxxxx Shielding hood...
  • Page 17: Line Plug-In Modules

    Line plug-in modules Line plug-in modules E3M060 line plug-in module 'MS9i' Item Component Preparation Default ex factory 'S3' programming switch: I bus ad- Set in accordance with system documentation Address 0 dress E3M071 'interactive' line plug-in module Allows up to 128 D bus devices to be connected, but only if all the devices used feature the 'A' designation (e.g.
  • Page 18: E3M171 'Interactive Ex' Line Plug-In Module

    Line plug-in modules E3M171 'interactive Ex' line plug-in module Item Component Preparation Default ex factory 'S3' programming switch: I bus ad- Set in accordance with system documentation Address 0 dress E3M080 'collective' line plug-in module Item Component Preparation Default ex factory 'S3' programming switch: I bus ad- Set in accordance with system documentation Address 0...
  • Page 19: E3M120 Line Plug-In Module 'Cba8000/Ts9000

    Line plug-in modules E3M120 line plug-in module 'CBA8000/TS9000' Item Component Preparation Default ex factory 'S1' programming switch: I bus ad- Set in accordance with system documentation Address 0 dress 'X1' bridge: Watchdog – attached 'in' -> watchdog active E3M140 'FD20' line plug-in module Item Component Preparation...
  • Page 20: E3M141 'Fd20' Line Plug-In Module

    Line plug-in modules E3M141 'FD20' line plug-in module Item Component Preparation Default ex factory 'I BUS ADR' programming switch: Set in accordance with system documentation Address 0 I bus address 'SYNC-MASTER' programming switch: if the line plug-in module is the master, set switch 1 to To 'OFF' Synchronization of alarm devices in 'ON'...
  • Page 21: Lon Plug-In Module

    LON plug-in module LON plug-in module E3I040 I bus/LON plug-in module Item Component Preparation Default ex factory 'S3' programming switch: I bus ad- Set in accordance with system documentation Address 0 dress 100 ς 'R60' resistor: 'LON bus' terminator If the LON bus is wired as free topology, 'R60' must be changed to 50 ς, see description in document resistor 001260...
  • Page 22: Control Plug-In Modules

    Control plug-in modules Control plug-in modules E3L020 'I/O' control plug-in module Item Component Preparation Default ex factory 'S3' programming switch: I bus ad- Set in accordance with system documentation Address 0 dress 'S2' service switch: Activate test LEDs Set to 'ON' for commissioning To 'OFF' 'H1'..'H16' E3L030 'VdS' control plug-in module...
  • Page 23: E3G050 'Contacts' Control Plug-In Module

    Control plug-in modules E3G050 'contacts' control plug-in module Item Component Preparation Default ex factory 'S3' programming switch: I bus ad- Set in accordance with system documentation Address 0 dress 'S2' service switch: Activate test LEDs Set to 'ON' for commissioning To 'OFF' 'H1'..'H8' E3G060 'monitored' control plug-in module...
  • Page 24: E3G070 'Universal' Control Plug-In Module

    Control plug-in modules E3G070 'universal' control plug-in module Item Component Preparation Default ex factory 'S3' programming switch: I bus ad- Set in accordance with system documentation Address 0 dress 'S2' service switch: Activate test LEDs Set to 'ON' for commissioning To 'OFF' 'H1'..'H11' 0 ς...
  • Page 25: Extinguishing

    Extinguishing Extinguishing For commissioning of extinguishing –> see document 009853 Building Technologies 008726_e_en_-- Fire Safety 06.2017...
  • Page 26: Peripheral Devices

    Peripheral devices Peripheral devices 10.1 E3G091 remote transmission interface Item Component Preparation Default ex factory 0 ς resistors 'X1-6', 'Y1-6': Define Possibly resolder according to system documentation, 'Y1/Y2' alarm/fault as normally see also description in document 001260 closed contact (NC) normally open contact (NO) / normally closed contact (NC) 'X3-X6' outputs as normally...
  • Page 27: Operation And Floor Repeater Display

    Operation and floor repeater display Operation and floor repeater display 11.1 B3Q... AlgoPilot operating terminal For operation of AlgoPilot B3Q..–> see pages 15 –16 11.2 B3Q321 fire brigade operating unit Item Component Preparation Default ex factory Shielding hood Remove (refit) Fitted 'S3' programming switch: I bus ad-...
  • Page 28: K3R072 Mimic Display Board

    Operation and floor repeater display 11.4 K3R072 mimic display board Item Component Preparation Default ex factory Mounting plate Remove, fit according to system documentation, see Fitted also description in document 001260 'N3' resistor array Remove from all but 1 device, also see description in Equipped document 001260 'S1' programming switch: Device...
  • Page 29: K3I050 Lon/Mimic Display Converter

    Operation and floor repeater display 11.6 K3I050 LON/mimic display converter Item Component Preparation Default ex factory Mounting plate Remove, fit according to system documentation, see Fitted also description in document 001260 'S3' programming switch: LON bus Set in accordance with system documentation Address 0 address 'S4-1' programming switch: Define...
  • Page 30: K3I110 Lon I/O Board

    Operation and floor repeater display 11.8 K3I110 LON I/O board Item Component Preparation Default ex factory 'S3' programming switch: LON bus Set in accordance with system documentation Address 0 address 'X30' bridge: Ground fault monitoring Set according to system documentation, see also To 'right' (not monitored) 'Inputs' description in document 001260...
  • Page 31: B3Q590/595 Plain Text Operating Terminal

    Operation and floor repeater display 11.10 B3Q590/595 plain text operating terminal Item Component Preparation Default ex factory 'S3' programming switch: LON bus Set in accordance with system documentation Address 0 address 'S4-1' programming switch: Buzzer off For 'S4-1' commissioning, set to 'ON' To 'OFF' 'R1' resistor: 'LON bus' terminator When using stub line: If B3Q5xx is not the last de-...
  • Page 32: Printer

    Printer Printer 12.1 K3L080 printer control (included and fitted in B2Q191 protocol printer) Item Component Preparation Default ex factory 'S1' programming switch: For Baud Set according to description in document 001260, To 'closed' rate, set of characters 'Protocol printer B2Q191' chapter 'X11/12' bridges: Define active inter- All plugged to '2-3' faces...
  • Page 33: Gateway

    Gateway Gateway 13.1 E3H020 C bus gateway Take measures to protect against overvoltage when inserting RAM and NOTE EPROMs. Press modules all the way into the base. Item Component Preparation Default ex factory RAM modules 'D11/12', 'D15/16' or – 4x512Kx8 bits RAM kit Z3S070 (2x 512Kx8 bits) Change RAM if necessary, see description in docu- ment 001260...
  • Page 34: E3H021 C Bus Gateway

    Gateway 13.2 E3H021 C bus gateway Item Component Preparation Default ex factory SRAM – 8x512Kx8 bits Flash ROM – Program file for E3H021 CK1142 CKX00xxx CK1143 CKY00xxx 'S3' programming switch: Set in accordance with system documentation All switches to 'OFF' Set station address 'S5' programming switch: Set according to system documentation, see also...
  • Page 35: Power Supply

    Power supply Power supply 14.1 B1F120/B2F020/B2F040/B2F060 converter Item Component Preparation Default ex factory Metal cover Remove – Bridge Important: Check voltage set, possibly, reconnect at 230 V AC mains voltage 115 V AC mains voltage Metal cover Refit – Converter (power supply unit) Fit in housing or on component carrier –...
  • Page 36: E3C011 Battery Charging Plug-In Module

    Power supply 14.2 E3C011 battery charging plug-in module Item Component Preparation Default ex factory 'S3' programming switch: I bus ad- Set in accordance with system documentation Address 0 dress 'S2' programming switch: Battery type Set to battery make used, see description in docu- 'ALARMCOM' (FIAMM) type selection ment 001260...
  • Page 37: Ground Fault Monitoring

    Ground fault monitoring Ground fault monitoring 15.1 Components with ground fault monitoring For detailed information about components with ground fault monitoring, use, func- tion and programming, see document 001260, 'Ground fault monitoring' chapter. The ground fault monitoring is inactive for all components, i.e. 'C bus potential' is not routed to 'system ground' –>...
  • Page 38: Inserting Plug-In Modules

    Inserting plug-in modules Inserting plug-in modules NOTE Do not under any circumstances connect I buses from different stations! Procedure 1. Insert plug-in modules (1) according to system documentation and lock. 2. Fit I bus flat cable (2) (ensure good contact). Never plug in or remove when en- ergized.
  • Page 39: Switching On For The First Time

    Switching on for the first time Switching on for the first time 1. Check whether the batteries are connected. 2. Establish mains voltage. Note 2 'Safety regulations' chapter. The 'CC'/'CI'/'CT' stations load basic configuration stored in the EPROM into – the RAM.
  • Page 40: Activating Interactive And Analogplus Devices

    Activating interactive and AnalogPLUS devices Activating interactive and AnalogPLUS devices 18.1 Automatic detectors DOW1171 RE6T DZ1193 RE10 LE3/StabexHF DZ1193 –> see document 1462 κ RE6/RE6T/RE10 –> see document 1164 κ –> see document 257 κ DF11.. –> see document 1673 κ...
  • Page 41: Input/Output Modules

    Activating interactive and AnalogPLUS devices 18.4 Input/output modules Item Input/output module Procedure DC11xx Addressing by order of installation – Addressing by inserting switching unit DC11xx-AA – Addressing by alarming, press button (3), the addressing is – indicated by the LED (4) flashing Building Technologies 008726_e_en_-- Fire Safety...
  • Page 42: Activating Sinteso Devices

    Activating Sinteso devices Activating Sinteso devices 19.1 Automatic detectors FDT... FDO... FDOOT... FDOOT... FDUD292 RE6T FDUD293 FDL... FDF... FDUD292 FDUD293 LE3/StabexHF FDLU291 FDUD292 –> see document 7227 κ FDUD293 –> see document 9718 κ RE6/RE6T/RE10 –> see document 1164 κ –>...
  • Page 43: Manual Call Point

    Activating Sinteso devices 19.2 Manual call point Item Manual call point Procedure FDM.. 'KAC' version Insert test key – Wait until the response indicator flashes – – Remove test key again FDM11... 'DIN' version Use key to open doors – Press button firmly –...
  • Page 44: Alarm Devices

    Activating Sinteso devices 19.4 Alarm devices FDUD292 FDUD293 Activating of alarm devices via FDUD29x is not possible. This can be done by activating the corre- sponding zone. Building Technologies 008726_e_en_-- Fire Safety 06.2017...
  • Page 45: Tool For Localization

    Tool for localization Tool for localization 20.1 Commissioning list for identifying devices Handheld list κ 01: demo system Area: 01: 2nd floor west Section: Detector Location ID number type laboratory 201 window left DO1151 95683489 DO1151 25897954 laboratory 201 window right Enter detector ID number, laboratory 201 door left DO1151...
  • Page 46 Issued by © Siemens Switzerland Ltd 2005-2017 Siemens Switzerland Ltd. Technical specifications and availability subject to change without notice. Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug, Switzerland +41 41 - 724 24 24 www.siemens.com/buildingtechnologies Document ID 008726_e_en_-- Manual CS11.2 Edition 06.2017...