Serial Printer Installation

The 7810iR-ent supports Okidata Microline 320 serial printers. The serial printer is
connected to 7810iR-ent using an RS232C link. All reports received by 7810iR-ent are also
printed on the connected printer. If a user manually acknowledges an alarm then "^^^ User
Ack ^^^" is printed after an alarm to indicate that the previous alarm was manually
acknowledged. The 7810iR-ent does not supervise the printer and will not generate any
alarm if the printer is out of paper or if the printer is disconnected.
ULC

Serial Printer Configuration

Printer should be configured as follows -
Parity (none), Serial Data (8 bits), Baud rate (19200 bps);

Serial Printer Connection Summary

7810iR-ent Pin
6
7
3 (Ground)
* Pins 6 and 20 are shorted; (DTR and DSR)

Sample Printer Output

The following is a sample printer output when 7810iR-ent is in Auto or Manual mode.
NOTE: The first character in the line indicates the source of the alarm. C = AlarmNet-C
Radio, P = Private LAN and I = Internet.
Sample output for Manual Mode (User Acknowledgement is required)
P 15:19:22 06/22/04 00 0020 18 E 339 00 C803
^^^ User Ack ^^^
P 15:19:33 06/22/04 00 0020 18 E 341 00 C803
^^^ User Ack ^^^
P 15:20:24 06/22/04 00 0020 18 E 355 00 C000
^^^ User Ack ^^^
Sample output for Auto Mode (User Acknowledgement is NOT required)
P 15:19:22 06/22/04 00 0020 18 E 339 00 C803
P 15:19:33 06/22/04 00 0020 18 E 341 00 C803
P 15:20:24 06/22/04 00 0020 18 E 355 00 C000
2-10
For UL installations, the DC power supply must be a UL Listed, regulated 12VDC, min. 500mA
Commercial Fire Alarm power supply, or two UL Listed Class 2 Honeywell Model 7720V2TRs
powered by a UL1481 Listed UPS with audible and visual indications of switchover to
secondary power.
For ULC installations, the DC power supply must be a CUL or CSA Listed, regulated 12VDC,
min. 500mA Commercial Fire Alarm power supply, or two UL Listed Class 2 Honeywell Model
7720V2TR-CNs powered by a CUL or CSA Listed Commercial Fire Alarm UPS with audible
and visual indications of switchover to secondary power.
Must use a ULC listed serial printer suitable for use in Central and Monitoring Stations.
(Such as a PRN-6 or PRN-6F serial printer.)
Connects to Printer DB25 Connector Pin
2 (TX)
3 (RX)
7 (Signal ground)