Section 3; Navigation And Basic Feature Tour; Home Screen - Honeywell AlarmNet 7810iR-ent Installation And Setup Manual

Internet/intranet ip alarm receiver
Table of Contents

Advertisement

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Home Screen

The 7810iR-ent uses a Graphical User Interface (GUI). The user programs and controls the
unit by pressing the required touch screen buttons.
The 7810iR-ent home screen is shown below. New incoming alarms are displayed using
Contact ID or ADEMCO high-speed format in the New Alarm Window. When a new alarm is
received it will be displayed in the New Alarm Window until the alarm is transmitted to the
line card or automation equipment, or manually acknowledged. When the alarm message is
transmitted, it is moved from the New Window to the Alarm History Window.
Display Next
Status displays for:
Private LAN, Mode,
and System
AlarmNet Setup
ITEM
Alarm History window
New Alarm window
Test button
Recovery Mode Status indicator
Time display/button
Silence Alert button
Manual Override box
AlarmNet Setup button
Private LAN, Mode, and System
status displays

Navigation and Basic Feature Tour

button
button
Manual Override
Silence Alert
button
box
FUNCTION
Displays cumulative alarm history.
Displays new alarms.
Used to send a test alarm in AlarmNet-i application. This has no
function in an enterprise application.
Enables the operator to see if the recovery mode is ON.
Flashing green light indicates that recovery mode is ON.
Displays the time.
Note: When accessed from Advanced Setup screen, it enables an
authorized operator to set time, date and time zone.
Used to silence new alarms and move them to the Alarm History
window.
allows the operator to quickly select manual
When checked,
mode while in either Line Card or Automation Mode if Fail to
Manual Mode is selected.
Used to access all the 7810iR-ent programmable features.
Used to indicate network status, operating mode and overall system
status, respectively. When used in an enterprise application where
the 7810iR-ent is not reporting to another Central Station, the
network status display will show AlarmNet Blocked. This is a normal
condition. If "Private LAN Only" LAN Config is selected then
network status display will show Private LAN.
S E C T I O N
Alarm History
window
New Alarm
window
Test button
Recovery Mode Status
indicator
Time display/button
3