7810iR-ent Internet/Intranet Alarm Receiver Installation and Setup Guide

Power Requirements

The 7810iR-ent requires a 12VDC, 500mA line input.
UL
ULC

Manual Mode

General Information

As the name implies, Manual Mode is a standalone method of receiving Contact ID or
ADEMCO high-speed messages from a protected premise. Incoming messages are displayed
in the New Alarm Window of the 7810iR-ent. An operator is required to silence an incoming
alarm and manually move it from the New Alarm window to the Alarm History window
using the appropriate touch keys on the GUI.
A programmable feature allows Manual Mode to be the 7810iR-ent failure mode. When
selected during programming, Fail to Manual allows the 7810iR-ent to automatically
revert to Manual Mode if the automation equipment or LRR line card fails. Fail to Manual
mode must be enabled for UL installations. Refer to Section 5 for a detailed description of
the Fail to Manual feature.

Wiring the 7810iR-ent for Manual Mode

There are two methods of powering the 7810iR-ent. You can use a UL Listed, regulated
12VDC, min. 500mA Commercial Fire Alarm power supply, or two UL Listed Class 2
Honeywell Model 7720V2TRs powered by a UL1481 Listed UPS. If using Model 7720V2TRs,
refer to Figure 1a, and connect as follows:
1. Connect the 12V AUX terminal (pin 1) of the 7810iR-ent to the DC (+) terminal of a
7720V2TR power supply.
2. Connect the 12V IN terminal (pin 2) of the 7810iR-ent to the DC (+) terminal of a second
7720V2TR power supply.
3. Connect the GND terminal (pin 3, BLK) of the 7810iR-ent to the DC (-) terminal of both
7720V2TR power supplies.
4. Connect one end of the Ethernet cable (Category 5) to the 7810iR-ent's RJ45 Ethernet
connector and the other end to an Ethernet router.
UL
5. Attach the case front of the 7810iR-ent to the case back. Attach the top of the 7810iR-ent
first, and then press the bottom section inward until it snaps into place securely.
NOTE: For more information on networking, refer to the Communications Setup Section.
For general information on the 7810iR-ent, refer to the Navigation and Basic Features
Section. To complete the installation, refer to the Programming Section.
2-2
For UL installations, the DC power supply must be a UL Listed, regulated 12VDC, min. 500mA
Commercial Fire Alarm power supply, or two UL Listed Class 2 Honeywell Model 7720V2TRs
powered by a UL1481 Listed UPS with audible and visual indications of switchover to
secondary power.
For ULC installations, the DC power supply must be a CUL or CSA Listed, regulated 12VDC,
min. 500mA Commercial Fire Alarm power supply, or two UL Listed Class 2 Honeywell Model
7720V2TR-CNs powered by a CUL or CSA Listed Commercial Fire Alarm UPS with audible
and visual indications of switchover to secondary power.
For AlarmNet you must use a UL Listed cable/DSL router (externally powered) suited for the
application.