Optional Single-Point Power Supply Connection And Individual System Circuit Breakers; Optional Single-Point Power Supply - York MILLENIUM YCAS Series Installation Operation & Maintenance
OPTIONAL SINGLE-POINT POWER SUPPLY WITH INDIVIDUAL SYSTEM CIRCUIT BREAKERS
(One field provided power supply circuit to the unit with circuit protection. Field connections to factory provided Non-Fused Disconnect Switch (Opt), or
Terminal Block (Opt) in the Options Panel. Factory connections to Terminal Blocks in each of the two Power Panels.)
Chiller
Model
Volts
MRA
1
Min. NF
YCAS
(MCA)
Disc Sw.
0283
380
197
0303
380
204
0323
380
238
0343
380
247
See page 56 for Electrical Notes.
50
ELECTRICAL DATA
LD06176
Field Provided Power Supply
Over-Current Protection
Min.
Max.
2, 9
3, 5
4, 6
200
200
225
200
225
250
250
250
300
250
300
300
OPTIONAL SINGLE-POINT POWER SUPPLY
CONNECTION AND INDIVIDUAL SYSTEM CIRCUIT
BREAKERS
Suitable for:
Y - ∆ ∆ ∆ ∆ ∆ Start and
Across-The-Line-Start
One field provided power supply circuit to the unit with
circuit protection. Field connections to factory provided
Non-Fused Disconnect Switch (Opt), or Terminal Block
(Opt) in the Options Panel. Factory connections to Ter-
R-134a centrifugal liquid chillers with optiviewtm control center for electro-mechanical starter, solid state starter & variable speed drive (36 pages)