Optional Single-Point Power Supply Connection And Internal Unit Circuit Breakers - York MILLENNIUM YCAS 250 Manual

Air cooled liquid chiller
Table of Contents

Advertisement

Technical Data
OPTIONAL SINGLE-POINT POWER SUPPLY
CONNECTION AND INTERNAL UNIT CIRCUIT
BREAKERS
OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION WITH INTERNAL UNIT CIRCUIT BREAKERS
(One Field Provided Power Supply Circuit to the chiller. Field connections to Power Terminal Block (standard) or Non-Fused Disconnect (option)
CHILLER
FIELD PROVIDED POWER SUPPLY
MODEL
YCAS VOLTS
MIN NF
1
MCA
DISC SW
2, 9
380
561
600
0250EC
460
464
600
575
372
400
380
651
800
0270EC
460
534
600
575
427
600
380
678
800
0300EC
460
559
600
575
445
600
380
745
800
0330EC
460
612
800
575
487
600
380
835
1000
0360EC
460
689
800
575
550
600
380
896
1000
0400EC
460
739
1000
575
589
800
380
991
1200
0440EC
460
812
1000
575
647
800
See page 54 for Electrical Data footnotes.
52
ELECTRICAL DATA
See Note 7 (page 54)
LD04744
in 'Option Panel'. Circuit Breakers in each Motor Control Center
FIELD SUPPLIED WIRING
OVER-CURRENT PROTECTION
13
MIN.
3, 5
MAX.
4, 6
600
700
500
500
400
450
800
800
600
700
500
500
800
800
600
700
500
500
800
800
700
700
600
600
1000
1000
800
800
600
600
1000
1000
800
800
700
700
1200
1200
1000
1000
800
800
Suitable for:
Y - ∆ ∆ ∆ ∆ ∆ Start and
Across-The-Line-Start
One field provided power supply circuit to the unit with
circuit protection. Field connections to factory provided
Non-Fused Disconnect Switch (Opt), or Terminal Block
(Opt) in the Options Panel. Factory connections to Cir-
cuit Breakers in each of the two Power Panels.
See Note 3
FACTORY PROVIDED (LUGS) WIRE RANGE
TERMINAL BLOCK
(LUGS) WIRE RANGE
(2) 2/0-500
(2) 1/0-300
(2) # 2-4/0
(2) 2/0-500
(2) 2/0-500
(2) 1/0-300
(3) 1/0-300
(2) 2/0-500
(2) 1/0-500
(3) 1/0-300
(2) 2/0-500
(2) 1/0-300
(3) 2/0-500
(3) 1/0-300
(2) 2/0-500
(3) 2/0-500
(3) 2/0-500
(2) 2/0-500
(3) 2/0-500
(3) 2/0-500
(2) 2/0-500
7
NF DISC. SWITCH
(LUGS) WIRE RANGE
(2) 250-500
(2) 250-500
(3) 2/0-250
(3) 2/0-400
(2) 250-500
(2) 250-500
(3) 2/0-400
(2) 250-500
(2) 250-500
(3) 2/0-400
(3) 2/0-400
(2) 250-500
(4) 4/0-500
(3) 2/0-400
(2) 250-500
(4) 4/0-500
(4) 4/0-500
(3) 2/0-400
(4) 4/0-500
(4) 4/0-500
(3 )2/0-400
YORK INTERNATIONAL

Advertisement

Table of Contents
loading

Table of Contents