MILLENNIUM CENTRIFUGAL LIQUID CHILLERS OPERATING & MAINTENANCE MODEL YK (STYLE D) R-134a (COOLING ONLY) WITH MICROCOMPUTER CONTROL CENTER PART #371-01200-010, 371-01200-011 & 371-01200-015 FOR ELECTRO-MECHANICAL STARTER, SOLID STATE STARTER & VARIABLE SPEED DRIVE 28815A WARNING SYSTEM CONTAINS REFRIGERANT UNDER PRESSURE.
Responsibility for assuring the satisfactory operation of other equipment included in the same power source as the YORK equipment rests solely with the user. YORK disclaims any liability resulting from any interference or for the correction thereof.
CONTROL CENTER CONTROL CENTER SERVICE ACCESS CODE CHARACTERISTIC DISPLAY PROGRAM STATUS MODE LOCAL, REMOTE SERVICE DISPLAY Service Local ENTRY COMPRESSOR Program Setpoint PROGRAM Remote SETPOINTS COMPRESSOR-START, RUN, STOP/RESET PROGRAM SWITCH REMOTE Entry OPERATION DISPLAYING SYSTEM PARAMETERS DISPLAY HOLD Display NOTE: If the display actually displays Xs, then the monitored parameter is out of normal operat- Display ing range (refer to Fig.
NOTE: The operating hours and starts counter can be reset to zero. Refer to Programming the Mi- croComputer Control Center, page 14. How- ever, the purpose of the OPERATING HOURS key is to display the total accumulated chiller run time. Therefore, the operating hours should not be arbitrarily reset.
Page 11
NOTE: If an Energy Management System is interfaced to the Control Center for the purpose of remote CLOCK LCWT setpoint reset, then the operator pro- grammed REMOTE RESET TEMP RANGE value determines the maximum value of tem- SUNDAY 12:00 AM 1/1/92 perature reset controlled by the Energy Man- agement System.
Page 12
The currently programmed Setpoint CURRENT LIMIT = XXX % FLA; *MTR CUR = 000 FLA SERVICE, LO- REMOTE NOTE: On Solid State Starter applications, this value is programmed at the YORK factory. A special Setpoint access code is required. Setpoint PULL DOWN DEMAND...
FRI START = 05:00 AM STOP = 07:00 PM UNDERVOLTAGE SAT START = 05:00 AM STOP = 01:00 PM (Solid State Starter Applications Only) HOL START = 00:00 AM STOP = 00:00 PM SSS MOTOR CURRENT/VOLTS PRO- GRAM HOLIDAY SUPPLY VOLTAGE RANGE 380 HOLIDAY SUPPLY VOLTAGE RANGE 400 S_ M_ T_ W_ T_ F_ S_ HOLIDAY NOTED BY *...
Page 14
PROGRAMMING THE MICROCOMPUTER CONTROL CENTER PROGRAMMING SYSTEM SETPOINTS ACCESS CODE ENTER VALID ACCESS CODE _ _ _ _ ENTRY 9 6 7 5 Y O R K NOTE: If digits other than 9 6 7 5 are entered, Y O R K is still displayed. NOTE: For ease in remembering the code, note that the letters Y O R K correspond to the LD00954...
Page 15
CURRENT LIMIT = XXX% FLA; MTR CUR = _ _ _ FLA ENTRY LD00956 NOTE: Motor Current FLA value is entered by YORK factory and checked at system start- FIG. 7 up. It cannot be changed without special access code. (Note to service technician: refer to Programming Instructions...
Page 16
PULL DOWN DEMAND PULL DOWN DEMAND SETPOINT = XXX MIN @ XXX % FLA, XXX MIN LEFT Entry PULL DOWN DEMAND ENTER PROGRAM MODE, SELECT SETPOINT LD00957 FIG. 8 CLOCK CLOCK TODAY IS MON 10:30 PM 1/1/92 ADVANCE DAY / SCROLL Entry AM/PM Entry...
Page 17
DAILY SCHEDULE ADVANCE DAY / SCROLL DAILY SCHEDULE ENTER SUN START = XX:XX AM, STOP = XX:XX AM PROGRAM MODE, SELECT SETPOINT CANCEL Entry AM/PM Entry AM/PM ADVANCE DAY/SCROLL MON START = XX:XX AM, STOP = XX:XX AM LD00959 ADVANCE DAY/SCROLL REPEAT MON SCHEDULE MON-FRI? YES = 1;...
Page 18
HOLIDAY HOLIDAY S_ M_ T_ W_ T_ F_ S_ HOLIDAY NOTED BY * ADVANCE DAY/SCROLL ENTER PROGRAM MODE, SELECT SETPOINT CANCEL ENTER LD00961 PROGRAM MODE, SELECT SETPOINT FIG. 11 ADVANCE DAY / SCROLL ENTER REMOTE/ RESET TEMP RANGE REMOTE/RESET TEMP RANGE REMOTE TEMP SETPOINT RANGE = XX °F Entry ENTER...
Page 19
SERVICE KEYS LD00963 FIG. 13 Service HOLD WARNING RE- SYSTEM RUN VANES HOLDING PRE-ROTATION VANES SERVICE Service SYS READY TO START VANES HOLDING SERVICE LOCAL REMOTE OPEN HOLD AUTO PRE-ROTATION VANES KEYS CLOSE SYSTEM RUN VANES CLOSING SYS READY TO START ...
Page 20
ING RESET WARNING RESET SERVICE OPEN COMPRESSOR STOP/RESET SYSTEM RUN LEVEL VALVE OPENING MANUAL OIL PUMP SYS READY TO START LEVEL VALVE OPENING CLOSE HOLD AUTO HOLD SYSTEM RUN LEVEL VALVE HOLDING SYS READY TO START LEVEL VALVE HOLDING DISPLAY DATA ...
Page 21
NO. 4 DISCHARGE TEMP = XXX.X°F; OIL TEMP = XXX.X°F NO. 5 NO. 2 HOP = XX.X PSIG; LOP = XX.X PSIG PULLDN LEVEL = XXX%; SETP = XXX%; ACTUAL = XXX% PULLDN LEVEL SETP NO. 6 ACTUAL ACTUAL POS ACTUAL POS = XX MILS;...
OPERATING MODES OPERATING MODES NOTE: If digits other than 9 6 7 5 are entered, Y O R K is still displayed. ENTER NOTE: If digits other than 9 6 7 5 were entered in SERVICE Service keys DIS- step No. 4, is dis- INVALID ACCESS CODE PLAY DATA, MANUAL OIL PUMP, HISTORY...
COMPRESSOR SWITCH RESET STOP/RESET START* LOCAL *NOTE: The operator cannot start the compressor (us- COMPRESSOR STOP/RESET ing this switch) when the Control Center is in START REMOTE mode. STOP STOP/RESET DISPLAY MESSAGES SERVICE AUTO SYSTEM RUN - CURRENT LIMIT IN EFFECT SYSTEM RUN ...
Page 24
SYS READY TO START VANES OPENING OPEN SYSTEM RUN HIGH PRESSURE LIMIT IN EFFECT SYS READY TO START VANES CLOSING CLOSE SYS READY TO START VANES HOLDING HOLD SYSTEM RUN PRESSURE STATUS SYSTEM RUN LEVEL VALVE OPENING STATUS WARNING: COND OR EVAP TRANSDUCER ERROR SERVICE...
SYSTEM READY TO START MON XX:XX AM SYSTEM CYCLING AUTOSTART STANDBY LUBE IN PROCESS - XXX.X MIN LEFT MON XX:XX AM MULTI UNIT CYCLING AUTOSTART SYSTEM SHUTDOWN PRESS STATUS MON XX:XX AM POWER FAILURE AUTOSTART COM- PRESSOR STOP/RESET...
Page 26
SYSTEM RUN LEAVING TEMP CONTROL COMPRESSOR STOP/ RESET START MON XX:XX AM OIL PUMP DRIVE AUTOSTART MON XX:XX AM INTERNAL CLOCK AUTOSTART COMPRESSOR START MON XX:XX AM LOW OIL PRESSURE REMOTE STOP COMPRESSOR STOP/ RESET START REMOTE...
Page 27
PRESSOR STOP/RESET START MON XX:XX AM HIGH OIL TEMP COMPRESSOR STOP/RESET START MON XX:XX AM HIGH OIL PRESSURE MON XX:XX AM MOTOR CONTROLLER EXT. RESET COMPRES- STOP/RESET START MON XX:XX AM FAULTY COND PRESSURE XDCR NOTE: The following motor controller shutdowns do not require an external reset to restart chiller.
Page 28
MON XX:XX AM PROGRAM INITIATED RESET MON XX:XX AM MTR PHASE CURRENT UNBALANCE COMPRESSOR STOP/ RESET START SYSTEM READY TO START PRESS STATUS ∅ ∅ ∅ STATUS SYSTEM READY TO START PRESS STATUS ∅ Service WARN- ING RESET MON XX:XX AM ...
Page 29
MON XX:XX AM PROX SENSOR SAFETY SHUTDOWN MON XX:XX AM LOW OIL TEMP DIFF AUTOSTART MON XX:XX AM LOW OIL TEMP DIFF AUTOSTART NOTE: With EPROM version C.02F (T).11, if the refer- ence position is < 42 mils, the minimum allowed distance is 22 mils.
Page 30
MON XX:XX AM OPEN DRAIN TEMP THERMOCOUPLE MON XX:XX AM AUX SAFETY SHUTDOWN COMPRESSOR STOP-RESET START IMPORTANT: REPLACE RTC. U16 REPROGRAM SETPOINTS REAL-TIME CLOCK MON XX:XX AM DC UNDERVOLTAGE 24673A FIG. 14 ...
SECTION 3 SYSTEM OPERATING PROCEDURES WARNING CAUTION: Comply with EPA and Local regulations when removing or disposing of Refrigera- tion System oil! START-UP PROCEDURE SERVICE LOCAL PRO- GRAM REMOTE SYSTEM READY TO START % CURRENT LIMIT CURRENT LIMIT = 100% FLA CURRENT LIMIT = 100% FLA, MTR CUR = XXXX FLA MANUAL OIL PUMP Service...
Page 32
DAY 10:30 AM LOW OIL PRESSURE DAY 10:30 AM HIGH OIL TEMPERATURE DAY 10:30 AM LOW OIL TEMP AUTOSTART DAY 11:30 AM OIL PRESSURE TRANSDUCER COMPRESSOR START STOP/RESET COMPRESSOR START NOTE: Any malfunctions which occur during STOP/RESET are also displayed.
SYSTEM STARTING & SHUTDOWN SEQUENCE OPERATOR INITIATED (NOTE 2) LD00952 FIG. 15 % CURRENT LIMIT NOTE: If the temperature setpoint has been repro- grammed within the last 10 minutes, the LWT cutout is 36°F (2.2°C) for 10 minutes. % CURRENT LIMIT Condenser Water Temperature Control MON 10:30 AM ...
OPERATING LOG SHEET 15 x % LOAD Min. ECWT = LCHWT—C RANGE + 5 + LD00467 23889A PRINT FIG. 16 ...
Page 35
STATUS OPERATING INSPECTIONS – See Section 2 Weekly Daily Quarterly OIL PRESSURE Semi-Annually (or more often as required) CONDENSER LIQUID TEMPERATURES Annually (more often if necessary) CHILLED LIQUID TEMPS REFRIGERANT PRESSURES DISPLAY DATA DISPLAY HOLD DATA DISPLAY...
Page 36
NEED FOR MAINTENANCE OR SERVICE SYSTEM SHUTDOWN – PRESS STATUS STATUS CYCLING SHUTDOWNS NORMAL AND SAFETY SYSTEM SHUTDOWNS SYSTEM SHUTDOWN – PRESS STATUS STATUS START SEQUENCE INITIATED SAFETY SHUTDOWNS STOPPING THE SYSTEM (See Fig. 3, page 6) COMPRESSOR STOP/RESET SYSTEM COASTDOWN...
CAUTION: Isolation of the refrigerant in this sytem must be performed by a qualified service technician. OPTIONAL HOT GAS BYPASS PULLDN LEVEL = XXX%; SETP = XXX%; ACTUAL = XXX% DISPLAY DATA NOTE: Changes in chilled water flow will require re- adjsutment of the hot gas control to insure proper operation.
Page 45
TABLE 1 SHUTDOWN CAUSE GOVERNING CONTROL FUNCTION CONTROL CENTER DISPLAY PROGRAMMED START-UP OF PROBABLE CAUSE OPERATING SETPOINTS SYSTEM AFTER AND SERVICE DAY OF TIME OF CAUSE OF METHOD OF POINT DESCRIPTION BY OPERATOR SHUTDOWN REQUIRED WEEK SHUTDOWN RESTART RISE FALL...
Page 47
TABLE 1 (Contd) SHUTDOWN CAUSE GOVERNING CONTROL FUNCTION CONTROL CENTER DISPLAY PROGRAMMED START-UP OF PROBABLE CAUSE OPERATING SETPOINTS SYSTEM AFTER AND SERVICE DAY OF TIME OF CAUSE OF METHOD OF POINT BY OPERATOR SHUTDOWN REQUIRED DESCRIPTION WEEK SHUTDOWN RESTART RISE FALL...
Page 48
TABLE 2 RESULTS POSSIBLE CAUSE REMEDY 1. SYMPTOM: ABNORMALLY HIGH DISCHARGE PRESSURE 2. SYMPTOM: ABNORMALLY LOW SUCTION PRESSURE 3. SYMPTOM: HIGH COOLER PRESSURE 4. SYMPTOM: NO OIL PRESSURE WHEN SYSTEM START BUTTON PUSHED 5. SYMPTOM: COMPRESSOR STARTS, NORMAL OIL PRESSURE DEVELOPS, FLUCTUATES FOR SHORT WHILE, THEN COMPRESSOR STOPS ON OIL PRESSURE CUTOUT LOW OIL PRESSURE...
Page 49
TABLE 2 RESULTS POSSIBLE CAUSE REMEDY 6. SYMPTOM: USUALLY HIGH OIL PRESSURE DEVELOPS WHEN OIL PUMP RUNS 7. SYMPTOM: OIL PUMP VIBRATES OR IS NOISY OIL PRESSURE 8. SYMPTOM: OIL PRESSURE GRADUALLY DECREASES (Noted by Observation of Daily Log Sheets) PRESSURE 9.
SECTION 7 MAINTENANCE RENEWAL PARTS CHECKING SYSTEM FOR LEAKS LEAK TESTING DURING OPERATION CONDUCTING R-22 PRESSURE TEST EVACUATION AND DEHYDRATION OF UNIT 27385A(D) LD00949 FIG. 21 ...
HANDLING REFRIGERANT FOR DISMANTLING AND REPAIRS MEGGING THE MOTOR NOTE: Motor is to be megged with the starter at ambient temperature after 24 hours of idle standby. LD00475 FIG. 23 ...
Page 55
Minimum Insulation Resistance vs. Temperature (per IEEE Std 43) Open Motors MEGOHMS...
CONDENSERS AND COOLERS GENERAL TUBE FOULING CHEMICAL WATER TREATMENT TUBE CLEANING PROCEDURES CLEANING COOLER AND CONDENSER TUBES WARNING: Acid cleaning should only be performed by an expert. Please consult your local water treatment representative for assistance in removing scale build-up and preventative maintenance programs to eliminate future problems.
COMMERCIAL ACID CLEANING NOTE: Do not use carbon tetrachloride for this pur- pose since its fumes give the same flame discoloration that the refrigerant does. TESTING FOR COOLER AND CONDENSER TUBE LEAKS...
PREVENTIVE MAINTENANCE COOLER AND CONDENSER IMPORTANT If a unit failure occurs due to improper maintenance during the war- ranty period; YORK will not be liable for costs incurred to return the system to satisfactory operation. COMPRESSOR COMPRESSOR MOTOR OIL RETURN SYSTEM...