OPTIONAL SINGLE-POINT POWER SUPPLY WITH INTERNAL UNIT CIRCUIT BREAKERS (See Fig. 15)
(One Field Provided Power Supply Circuit to the chiller. Field connections to Power Terminal Block or Non-Fused Disconnect in 'Option Panel'.
CHILLER
FIELD PROVIDED POWER SUPPLY
MODEL
VOLTS
MIN NF
YCAR
MCA
1
DISC SW
YCAR0315
380
230.3
YCAR0345
380
261.5
YCAR0365
380
286.5
YCAR0385
380
305.0
YCAR0415
380
325.6
YCAR0435
380
366.9
YCAR0485
380
399.9
YCAR0525
380
429.9
YCAR0575
380
455.0
YCAR0645
380
511.5
YCAR0685
380
551.5
See page 53 for Electrical Data footnotes.
56
ELECTRICAL DATA
Internal Branch Circuit Protection (Breakers)
OVER-CURRENT PROTECTION
2
3, 5
4, 6
MIN.
MAX.
250
300
300
400
300
350
400
350
400
400
350
400
400
400
450
400
450
500
600
450
500
600
500
600
600
600
600
600
600
700
600
700
700
10
per Compressor)
FIELD-SUPPLIED WIRING
FACTORY PROVIDED (LUGS) WIRE RANGE
13
STANDARD
TERMINAL BLOCK
2AWG - 300KCM
1/0 - 500KCM
1/0 - 500KCM
1/0 - 500KCM
1/0 - 500KCM
1/0 - 500KCM
1/0 - 500KCM
(2) 2AWG - 300KCM
(2) 2AWG - 300KCM
(2) 1/0 - 500KCM
(2) 1/0 - 500KCM
FORM 150.52-NM2 (1001)
7
OPTIONAL NF
DISC. SWITCH
6AWG - 350KCM
(2) 3/0 - 250KCM
(2) 3/0 - 250KCM
(2) 3/0 - 250KCM
(2) 3/0 - 250KCM
(2) 3/0 - 250KCM
(2) 250KCM - 500KCM
(2) 250KCM - 500KCM
(2) 250KCM - 500KCM
(2) 250KCM - 500KCM
(2) 250KCM - 500KCM