Technical Data
OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION TO FACTORY CIRCUIT BREAKER
(One field provided power supply circuit to the unit with circuit protection. Field connections to factory provided Circuit Breaker in the Options Panel. Factory
Model
Volts
MRA
1
YCAS
(MCA)
0283
380
197
0303
380
204
0323
380
238
0343
380
247
NOTES: Wye-Delta Compressor Start not available with this
option.See page 56 for Electrical Notes.
54
ELECTRICAL DATA
connections to Terminal Blocks in each of the two Power Panels.)
FIELD SUPPLIED WIRING
Factory Supplied Breaker
Rating
2,9
Wire Range
7
(Lugs)
225
# 14 - 250
250
# 14 - 250
300
# 14 - 250
300
# 14 - 250
OPTIONAL SINGLE-POINT POWER SUPPLY

CONNECTION TO FACTORY CIRCUIT BREAKER

Suitable for:
Across-The-Line-Start
One field provided power supply circuit to the unit with
circuit protection. Field connections to factory provided
Circuit Breaker in the Options Panel. Factory connections
to Terminal Blocks in each of the two Power Panels.
LD06178
SYSTEM #1
Compressor
Fans
11, 12
RLA
X-LRA Qty FLA(ea) LRA(ea) RLA
68.0
523
3
4.4
17.1
71.0
523
3
4.4
17.1
98.0
732
3
4.4
17.1
105.0
732
3
4.4
17.1
SYSTEM #2
Compressor
Fans
11, 12
X-LRA
Qty FLA(ea) LRA(ea)
68.0
523
3
4.4
17.1
71.0
523
3
4.4
17.1
71.0
523
3
4.4
17.1
71.0
523
3
4.4
17.1
YORK INTERNATIONAL