Electrical Data; Multiple Point Power Supply Connection - 2 Compressor Units; Optional Single-Point Power Supply Connection With Individual System Circuit Breakers - York eco2 YCAS0425EB Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

Technical Data
MULTIPLE POINT POWER SUPPLY CONNECTION – 2 COMPRESSOR UNITS (SEE FIG. 16)
(Each of Two Field Provided Power Supply Circuits individually protected with Branch Circuit Protection.
Field Connections to Factory provided Terminal Block (Std), Disconnects (Opt), or Individual System Circuit Breakers* (Opt)
Model
1
Volts MRA
Min. NF
YCAS
(MCA) Disc. Sw.
2, 9
0425EB
380
152
150
0475EB
380
205
200
0515EB
380
205
200
0555EB
380
255
250
0575EB
380
255
250
0605EB
380
241
250
* "Optional" Circuit Breakers are REQUIRED for units with CE mark.
See page 55 for Electrical Data Notes.
WITH INDIVIDUAL SYSTEM CIRCUIT BREAKERS – 2 COMPRESSOR UNITS (SEE FIG. 17)
One Field Provided Power Supply Circuit to the chiller. Field connections to Power Terminal Block or Non-Fused Disconnect
CHILLER
FIELD PROVIDED POWER SUPPLY
MODEL
MIN NF
YCAS
1
MRA
DISC SW
0425EB
304
400
0475EB
356
400
0515EB
409
400
0555EB
459
600
0575EB
509
600
0605EB
481
600
See page 55 for Electrical Data footnotes.
50

ELECTRICAL DATA

in each of the two Motor Control Centers.)
ELECTRICAL SYSTEM #1 FIELD SUPPLIED WIRING
Overcurrent
Factory Provided (Lugs) Wire Range
13
Protection
*Standard Terminal
Min.
3, 5
Max.
4, 6
Block
200
250
# 2 - 300
250
350
2/0 - 500
250
350
# 2 - 300
350
400
2/0 - 500
350
400
2/0 - 500
300
400
2/0 - 500
OPTIONAL SINGLE-POINT POWER SUPPLY
in 'Option Panel'. Internal Branch Circuit Protection (Breakers) per Motor Control Center
OVER-CURRENT PROTECTION
2,9
MIN.
3, 5
MAX.
350
350
400
450
450
500
500
600
600
600
500
600
7
*Optional NF.
Optional
Disc Switch
Circuit Breaker
# 6 - 250
# 6 - 250
# 6 - 300
(2) 3/0 - 250
# 6 - 300
# 6 - 350
# 6 - 350
(2) 3/0 - 250
# 6 - 350
(2) 3/0 - 250
# 6 - 350
(2) 3/0 - 250
FIELD-SUPPLIED WIRING
FACTORY PROVIDED (LUGS) WIRE RANGE
STANDARD
4, 6
TERMINAL BLOCK
(2) # 2 - 300
(2) # 1 - 500
(2) # 2 - 300
(2) # 1 - 500
(2) # 1 - 500
(2) # 1 - 500
11, 12
Compressor
Fans
FLA
LRA
RLA Y-LRA X-LRA Qty.
(Ea.) (Ea.)
106
217
690
4
4.8
23.0
148
267
857
4
4.8
23.0
148
267
857
4
4.8
23.0
188
267
857
4
4.8
23.0
188
267
857
4
4.8
23.0
173
267
857
5
4.8
23.0
10
.
7
OPTIONAL NF
DISC. SWITCH
(2) 3/0-250
(3) 2/0-400
(2) 3/0-250
(3) 2/0-400
(3) 2/0-400
(3) 2/0-400
YORK INTERNATIONAL