Over-current
Model
Volts
MRA
Min. NF
1
YCAS
(MCA) Disc. Sw.
Min.
2,9
0283
380
99
100
125
0303
380
102
100
125
0323
380
102
100
125
0343
380
102
100
125
YORK INTERNATIONAL
ELECTRICAL DATA
SYSTEM #2 FIELD-SUPPLIED WIRING
Factory Provided (Lugs) Wire Range
Protection
13
Std. Terminal
Max.
3, 5
4, 6
Block
150
# 18 - # 2
150
# 18 - # 2
150
# 18 - # 2
150
# 18 - # 2
7
Optional NF.
Optional
Disc. Sw.
Circuit Breaker
# 14 - 250
# 14 - 250
# 14 - 250
# 14 - 250
# 14 - 250
# 14 - 250
# 14 - 250
# 14 - 250
FORM 201.18-NM6
Compressor
Fans
11, 12
FLA
LRA
RLA Y-LRA
X-LRA Qty.
(Ea.) (Ea.)
68
175
523
3
4.4
17.1
71
175
523
3
4.4
17.1
71
175
523
3
4.4
17.1
71
175
523
3
4.4
17.1
49
7