Optional Single Point Power Supply Connection And Individual System Circuit Breakers; Fig. 19 - Optional Single-Point Power Supply Connection With Individual System Circuit Breakers - York YCAS Series Installation Operation & Maintenance

Air-cooled screw liquid chillers
Hide thumbs Also See for YCAS Series:
Table of Contents

Advertisement

Technical Data
Technical Data
OPTIONAL SINGLE POINT POWER SUPPLY
CONNECTION AND INDIVIDUAL SYSTEM CIRCUIT
BREAKERS
CB
1
CB
3
See notes below.
FIG. 19 – OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION WITH INDIVIDUAL
SYSTEM CIR CUIT BREAK ERS
NOTES:
1. – – – – – – – Dashed Line indicates Field Provided Wiring.
2. The above recommendations are based on the National Electrical Code and using copper conductors only.
Field wiring must also comply with local codes.
WITH INDIVIDUAL SYSTEM CIRCUIT BREAKERS – 3 AND 4 COMPRESSOR UNITS (SEE FIG. 19)
One Field Provided Power Supply Circuit to the chiller. Field connections to Factory Provided Terminal Block (standard) or Non-Fused Disconnect (option)
CHILLER
FIELD PROVIDED POWER SUPPLY
MODEL
MIN NF
YCAS
MRA
1
DISC SW
482
600
0685EB
517
600
0775EB
560
600
0835EB
637
800
0905EB
625
800
0965EB
669
800
1065EB
745
800
1135EB
822
1000
1215EB
See page 54 for Electrical Data footnotes.
52
ELECTRICAL DATA
CB
2
CB
4
OPTIONAL SINGLE POINT POWER SUPPLY CONNECTION
in the Options Panel. Individual System Circuit Breakers in each Motor Control Center.
OVER-CURRENT PROTECTION
MIN.
MAX.
2,9
3, 5
4, 6
600
600
600
600
700
700
700
700
800
800
700
700
800
800
1000
1000
Suitable for:
Y - ∆ Start and
Across-The-Line-Start
One fi eld provided power sup ply cir cuits to the unit with
in di vid u al branch cir cuit protection. Field Power Wiring con-
nections to fac to ry provided, Non-Fused Dis con nect Switches
(Opt), or Ter mi nal Blocks (Opt) in the Option Box.
Suitable for:
Y - D Start and
Across the Line Start
TB
or
Field Supply
DS
LD05554
FIELD-SUPPLIED WIRING
FACTORY PROVIDED (LUGS) WIRE RANGE
STANDARD
TERMINAL BLOCK
(2) 2/0 - 500
(2) 2/0 - 500
(2) 2/0 - 500
(3) 1/0 - 300
(3) 1/0 - 300
(3) 2/0 - 500
(3) 2/0 - 500
(3) 2/0 - 500
FORM 201.19-NM8 (804)
See Note 3
See Note 3 on
page 54.
7
OPTIONAL NF
DISC. SWITCH
(2) 250 - 500
(2) 250 - 500
(2) 250 - 500
(3) 2/0 - 400
(3) 2/0 - 400
(3) 2/0 - 400
(4) 4/0 - 500
(4) 4/0 - 500
YORK INTERNATIONAL