Page 3
Internal Unit Circuit Breakers ......52 Process and Instrumentation Diagram ....123 Electrical Notes ............54 Component Locations – 3 Compressor Units ... 124 Compressor Data ............. 55 Component Locations – 4 Compressor Units ... 125 Fan Data ..............55 YORK INTERNATIONAL...
Page 4
Chilled Liquid Temps Key ..................156 System # Data Keys ....................157 Ambient Temp Key ....................157 Motor Current Key ....................157 Operating HRS / Start Counter Key ..............158 Options Key & Dip Switch Settings ..............158 Function Key ......................160 YORK INTERNATIONAL...
Center. See Commissioning, page 41. specified in this manual. • Only genuine YORK approved spare parts, oils and This manual and the Microprocessor Operating Instruc- refrigerants must be used. Recommendations on tions contain all the information required for correct spare parts can be found on page 189.
This manual and any other document supplied with the unit, are the property of YORK which reserves all rights. Electrical They may not be reproduced, in whole or in part, with- The unit must be grounded.
Refrigerants and oils used in the unit are generally non- tem in an emergency. When operated, it removes the toxic, non-flammable and non-corrosive, and pose no electrical supply from the control system, thus shutting special safety hazards. Use of gloves and safety glasses down the unit. YORK INTERNATIONAL...
Fire Extinguishing Data Non-flammable. Containers Fire exposed containers should be kept cool with water sprays. Containers may burst if overheated. Fire Fighting Self contained breathing apparatus and protective clothing must be worn in fire conditions. Protective Equip. YORK INTERNATIONAL...
Page 10
General Chiller Information & Safety MATERIAL SAFETY DATA Section 1 – PRODUCT NAME AND INFORMATION Product (Trade Name and Synonyms): YORK “L” Oil Chemical Name: Ester Chemical Family: Polyol Ester Formula: Proprietary CAS#: Proprietary Section 2 – COMPONENTS AND HAZARD STATEMENT This product is non-hazardous.
Page 11
The information in this material safety data sheet should be provided to all who use, handle, store, transport, or are otherwise exposed to this product. CPI believes the information in this document to be reliable and up to date as of the date of publication, but makes no guarantee that it is. YORK INTERNATIONAL...
INTRODUCTION All exposed power wiring is be routed through liquid- tight, non-metallic conduit. YORK YCAS Millennium chillers are designed for water or water-glycol cooling. All units are designed to General Description be located outside on the roof of a building or at ground The Air Cooled Screw Chiller utilizes many compo- level.
Condenser The fin and tube condenser coils are manufactured from seamless, internally enhanced, high condensing coeffi- LD03674 cient, corrosion resistant copper tubes arranged in stag- FIG. 2 – SCREW COMPRESSOR YORK INTERNATIONAL...
15 ton TXV set for 10°F (5.5°C) superheat that flashes off 10 - 20% of the liquid from the condenser. 10 - 12 The oil (YORK “L” oil – a POE oil used for all refrig- tons are utilized for subcooling liquid refrigerant. The...
Compressor and fan starting contactors, fan motor ex- that could cause excessive motor current. This is ac- ternal overloads, control circuit serving compressor ca- complished by sending 3-phase current signals propor- YORK INTERNATIONAL...
Wye-Delta) and the number of wires in each phase flashing alphanumeric value which can be decoded by that are routed through the C.T. the operator. A list of the codes follows: YORK INTERNATIONAL...
As indicated, to place a switch in the ON position re- quires pushing the switch to the left. Imbalance is defined as (High Phase - Low Phase)/High Phase It is recommended that an YORK Ser- vice Technician or the YORK factory Improper Phase Sequence be consulted before changing these...
1S/2S and closes the normally closed 1S (SYS The standard display language is English, with 4 other 1) or 2S (SYS 2) contacts, energizing motor contactor languages available. 2M (SYS 1) or 4M (SYS 2), completing the “DELTA” connection of the motor. YORK INTERNATIONAL...
The supply with rent unload point, liquid temperature setpoint reset sig- appropriate branch circuit protection in accordance with nal from YORK ISN or building automation system. applicable Local codes, provides the unit control cir- cuit power supply via the panel mounted Emergency Additional functions (password protected) for program- Stop Switch.
1.0 g accelerated guards mounted on the exterior of the unit (Factory or force in all directions to 2" (51 mm). Level adjustable, field mounted). deflection may vary slightly by application. (Field mounted). YORK INTERNATIONAL...
If the unit is to be put into storage, prior to installation, Major damage must be reported immediately to your the following precautions should be observed: local YORK representative. MOVING THE CHILLER • Unit must be “blocked” so that the base is not Prior to moving the unit, ensure that the installation permitted to sag or bow.
The channels should be spaced at the same centres as lence interfering with the unit airflow. the vibration mounting holes in the unit base frame and must be at least 4-3/4" (120 mm) wide at the contact YORK INTERNATIONAL...
1" N.P.T. connection can be obtained On adjustable mounts, transfer the unit weight evenly from YORK as an accessory for the unit. Alternatively to the springs by turning the mount adjusting nuts (lo- a differential pressure switch sited across an orifice plate cated just below the top plate of the mount) counter- may be used, preferably of the high/low limit type.
Aerated, brackish or salt water is not recommended for installed to allow flushing of the pipework system. The use in the water system(s). YORK recommends that a by-pass can be used during maintenance to isolate the water treatment specialist is consulted to determine that heat exchanger without disrupting flow to other units.
Units are supplied with outlet guards for safety and to danger or cause injury. For indoor installations pres- prevent damage to the fan blades. If these guards are sure relief valves should be piped to the exterior of the removed to fit ductwork, adequate alternative precau- building. YORK INTERNATIONAL...
Terminals 29 and 30 (Figs. 11 and 12, pages 39 and 40) remote offset of EMS% CURRENT LOAD LIMIT. See close to indicate that a system is running. Figs. 11 and 12, pages 39 and 40 for contact location. YORK INTERNATIONAL...
Compressor Oil mary tapping has been used: To add oil to a circuit - connect a YORK hand oil pump (Part No. 470-10654-000) to the 1/4" oil charging valve With the supply to the unit isolated remove the lid to on the oil separator piping with a length of clean hose the transformer box.
Page 42
‘Remote Reset Temp’ key. into the control panel correctly using shielded cable. (See Section 6.) There should be a straight run of at least 5 pipe diam- eters on either side of the flow switch. The flow switch YORK INTERNATIONAL...
‘ON’ po- erant is in the system, the bubbles will disappear and sition and restart the unit. be replaced by a solid column of liquid. YORK INTERNATIONAL...
The units are designed to work independently, or in con- automatic. After an initial period at minimum capacity junction with other equipment via a YORK ISN build- on the lead compressor, the control system will adjust ing management system or other automated control sys- the unit load depending on the chilled liquid tempera- tem.
1.10 1.05 A = Correction Factor B = Mean Temperature through Cooler C = Concentration W/W PROPYLENE GLYCOL Excessive flow, above the max GPM, will damage the evaporator. LD03504 FIG. 14 – GLYCOL CORRECTION FACTORS YORK INTERNATIONAL...
1. For leaving brine temperature below 40°F (4.40°C), contact your nearest YORK office for application requirements. 2. For leaving water temperature higher than 55°F (12.8°C) contact the nearest YORK office for application guidelines. 3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
Evaporator, Direct Expansion Water Volume, gallons Maximum Water Side Pressure, PSIG Maximum Refrigerant Side Pressure, PSIG Minimum Chilled Water Flow Rate, GPM Maximum Chilled Water Flow Rate, GPM 1060 1060 1060 Water Connections, inches 1 Optional 300PSIG Waterside available YORK INTERNATIONAL...
Maximum Water Side Pressure, Bar Maximum Refrigerant Side Pressure, Bar 20.7 20.7 20.7 20.7 20.7 20.7 20.7 Minimum Chilled Water Flow Rate, l/sec. Maximum Chilled Water Flow Rate, l/sec. Water Connections, inches 1 Optional 21 Bar Waterside available YORK INTERNATIONAL...
ELECTRICAL THREE PHASE 60 Hz (V) ELECTRICAL THREE PHASE 60 Hz (V) * Maximum Ambient w/ High Ambient Kit is 130°F. * Maximum Ambient w/ High Ambient Kit is 54°C. SOUND POWER DATA (PRELIMINARY) MODEL YCAS 0250EC 0270EC 0300EC 0330EC 0360EC 0400EC 0440EC YORK INTERNATIONAL...
2. — — — — — Dashed Line = Field Provided Wiring. 3. The above recommendations are based on the National Electrical Code and using copper connectors only. Field wiring must also comply with local codes. *Group Rated breaker must be HRCR type for cU.L. machines. YORK INTERNATIONAL...
WYE-DELTA INRUSH LOCKED ROTOR AMPS CONTROL POWER SUPPLY (UNITS WITHOUT STANDARD CONTROL CIRCUIT TRANSFORMER) CONTROL MAX DUAL NON-FUSED NO. OF POWER (MAX LOAD ELEMENT DISCONNECT COMPRESSORS SUPPLY CURRENT) FUSE SIZE SWITCH SIZE 115V-1Ø 3 or 4 115V-1Ø (Non-CE 50/60Hz) (CE 50Hz) 115V-1Ø YORK INTERNATIONAL...
(C5N, C5E, C6N, C6E) VOLTAGE CODE -50 -58 MAX KW 80 105 MAX AMPS 135 118 TABLE 3 – FAN DATA (-46) NOMINALPOWER FULL LOAD AMPS LOCKED ROTOR AMPS FAN TYPE (kW) (FLA) (LRA) STANDARD 1.57 18.0 HIGH PRESSURE 46.3 YORK INTERNATIONAL...
(Class 2) Connections. See Note 2 shown, install a cycling device in series with the flow switch (FSLW). See Note 3 for contact rating and wiring Terminal Block for YORK Connections Only specifications. Also refer to cautions on page 63A. Wiring and Components by YORK 5.
STANDARD 3 COMPRESSOR POWER SUPPLIES WYE-DELTA START (PRESENT ON CERTAIN MODEL CHILLERS) (NOT PRESENT ON 3-COMPRESSOR CHILLERS) (PRESENT ON CERTAIN MODEL CHILLERS) (NOT PRESENT ON 3-COMPRESSOR CHILLERS) LD04174 FIG. 18 – STANDARD 3 COMPRESSOR POWER SUPPLIES - WYE-DELTA START YORK INTERNATIONAL...
Technical Data WIRING DIAGRAM ACROSS-THE-LINE START (PRESENT ON CERTAIN MODEL CHILLERS) (NOT PRESENT ON 3-COMPRESSOR CHILLERS) (PRESENT ON CERTAIN MODEL CHILLERS) (NOT PRESENT ON 3-COMPRESSOR CHILLERS) LD04173 FIG. 19 – ELEMENTARY DIAGRAM – ACROSS-THE-LINE START YORK INTERNATIONAL...
Page 61
FORM 201.18-NM3 This page intentionally left blank. YORK INTERNATIONAL...
Technical Data STANDARD COMPRESSOR POWER SUPPLIES ACROSS-THE-LINE START & WYE-DELTA START LD04175 FIG. 20 – ELEMENTARY DIAGRAM YORK INTERNATIONAL...
Page 63
Any contacts connected to flow switch inputs or BAS inputs on terminals 13 - 19 or TB3, or any other terminals, must be suppressed with a YORK P/N 031-00808-000 suppressor across the relay/ contactor coil. CAUTION: Control wiring connected to the control panel should never be run in the same conduit with power wiring.
Page 64
Technical Data FORM 201.18-NM3 CONNECTION DIAGRAM FIG. 21 – CONNECTION DIAGRAM LD04178 YORK INTERNATIONAL YORK INTERNATIONAL...
Page 65
FORM 201.18-NM3 LD04179 YORK INTERNATIONAL...
FORM 201.18-NM3 ELEMENTARY DIAGRAM DXST DIRECT DRIVE CONTROL CIRCUIT LD04177 FIG. 26 – ELEMENTARY DIAGRAM, DXST DIRECT DRIVE - CONTROL CIRCUIT YORK INTERNATIONAL...
Page 70
Technical Data ELEMENTARY DIAGRAM DXST DIRECT DRIVE CONTROL CIRCUIT LD04373 FIG. 27 – ELEMENTARY DIAGRAM, DXST DIRECT DRIVE - CONTROL CIRCUIT YORK INTERNATIONAL...
Page 71
FORM 201.18-NM3 ELEMENTARY DIAGRAM DXST DIRECT DRIVE CONTROL CIRCUIT DETAIL "C" SEE INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR JUMPER OF CONDENSER FANS FOR CHILLER MODEL LD04374 FIG. 28 – ELEMENTARY DIAGRAM, DXST DIRECT DRIVE - CONTROL CIRCUIT YORK INTERNATIONAL...
Technical Data CONNECTION DIAGRAM SYSTEM WIRING STANDARD & REMOTE EVAP. UNITS LD04184 FIG. 29 – CONNECTION DIAGRAM SYSTEM WIRING YORK INTERNATIONAL...
Page 73
FORM 201.18-NM3 CONNECTION DIAGRAM SYSTEM WIRING STANDARD & REMOTE EVAP. UNITS LD04185 FIG. 30 – CONNECTION DIAGRAM SYSTEM WIRING YORK INTERNATIONAL...
(Class 2) Connections. See Note 2 switching 24VDC. (Gold contacts recommended.) Con- trol Wiring must not be run in the same conduit with any Terminal Block for YORK Connections Only line voltage wiring. Wiring and Components by YORK 4. To cycle unit ON and OFF automatically with contact...
Technical Data STANDARD COMPRESSOR POWER SUPPLIES ACROSS-THE-LINE START (YCAS0360 - YCAS0440) LD04261 FIG. 35 – STANDARD POWER SUPPLY - ACROSS-THE-LINE START YORK INTERNATIONAL...
Page 79
FORM 201.18-NM3 This page intentionally left blank. YORK INTERNATIONAL...
Technical Data STANDARD COMPRESSOR POWER SUPPLIES (YCAS0360 - YCAS0440) ACROSS-THE-LINE START & WYE-DELTA START LD04257 FIG. 36 – STANDARD COMPRESSOR POWER SUPPLIES - ACROSS-THE-LINE START AND WYE-DELTA START YORK INTERNATIONAL...
Page 81
FORM 201.18-NM3 FORM 201.18-NM3 LD04258 FIG. 36 – STANDARD COMPRESSOR POWER SUPPLIES - ACROSS-THE-LINE AND WYE-DELTA START (CONT’D) YORK INTERNATIONAL YORK INTERNATIONAL...
Page 82
Technical Data FORM 201.18-NM3 This page intentionally left blank. This page intentionally left blank. LD04265 YORK INTERNATIONAL YORK INTERNATIONAL...
Page 83
FORM 201.18-NM3 This page intentionally left blank. YORK INTERNATIONAL...
Technical Data CONNECTION DIAGRAM SYSTEMS 1 & 2 FIG. 37 – CONNECTION DIAGRAM – WYE-DELTA START LD04265 YORK INTERNATIONAL...
Page 85
Any contacts connected to flow switch inputs or BAS inputs on terminals 13 - 19 or TB3, or any other terminals, must be sup- pressed with a YORK P/N 031- 00808-000 suppressor across the relay/contactor coil. CAUTION: Control wiring connected to the...
Page 86
Technical Data FORM 201.18-NM3 CONNECTION DIAGRAM SYSTEMS 3 & 4 FIG. 38 – CONNECTION DIAGRAM LD04267 YORK INTERNATIONAL YORK INTERNATIONAL...
Page 87
FORM 201.18-NM3 LD04268 YORK INTERNATIONAL...
Technical Data ELEMENTARY DIAGRAM DXST DIRECT DRIVE CONTROL CIRCUIT LD04177 FIG. 41 – ELEMENTARY DIAGRAM, DXST DIRECT DRIVE - CONTROL CIRCUIT YORK INTERNATIONAL...
Page 91
FORM 201.18-NM3 ELEMENTARY DIAGRAM DXST DIRECT DRIVE CONTROL CIRCUIT LD04695 FIG. 42 – ELEMENTARY DIAGRAM, DXST DIRECT DRIVE - CONTROL CIRCUIT YORK INTERNATIONAL...
Page 92
Technical Data ELEMENTARY DIAGRAM DXST DIRECT DRIVE CONTROL CIRCUIT DETAIL "C" SEE INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR NUMBER OF CONDENSER FANS FOR CHILLER MODELS LD04757 FIG. 43 – ELEMENTARY DIAGRAM, DXST DIRECT DRIVE - CONTROL CIRCUIT YORK INTERNATIONAL...
FORM 201.18-NM3 CONNECTION DIAGRAM SYSTEM WIRING STANDARD & REMOTE EVAP. UNITS LD04269 FIG. 44 – CONNECTION DIAGRAM SYSTEM WIRING YORK INTERNATIONAL...
Page 94
Technical Data CONNECTION DIAGRAM SYSTEM WIRING STANDARD & REMOTE EVAP. UNITS LD04270 FIG. 45 – CONNECTION DIAGRAM SYSTEM WIRING YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pressure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
Page 97
2-1/4" DIA. RIGGING 10" 10" (BOTH SIDES) (BOTH SIDES) WATER INLET WATER INLET HOLES (EACH SIDE) HOLES (EACH SIDE) WATER OUTLET WATER OUTLET 104" 104" 68" 68" 67-7/16" 67-7/16" 89-11/16" 89-11/16" 63-9/16" 63-9/16" 342-1/4" 342-1/4" SIDE VIEW SIDE VIEW LD03966 YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pres- sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
Page 99
3670 1066 1023 2438 1981 SYS. #3 SYS. #1 & #2 10" POWER OPENING 10" (4) 57 DIA. RIGGING WATER INLET (BOTH SIDES) WATER OUTLET HOLES (EACH SIDE) 3708 2642 1614 1727 2277 1713 8694 SIDE VIEW LD03970 YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pressure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
Page 101
36" 96" 78" 2" SYS. #3 SYS. #1 & #2 10" POWER OPENING 7-1/2" 10" (4) 2-1/4" DIA. RIGGING WATER OUTLET (BOTH SIDES) HOLES (EACH SIDE) WATER INLET 146" 104" 68" 115-7/16" 63-9/16" 89-11/16" 390-1/4" SIDE VIEW LD03982 YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pres- sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
Page 103
3982 1065 1051 2438 1981 SYS. #3 SYS. #1 & #2 (4) 57 DIA. RIGGING POWER OPENING 10" 10" HOLES (EACH SIDE) (BOTH SIDES) WATER INLET WATER OUTLET 3708 2642 2277 1727 2932 1614 9913 SIDE VIEW LD03986 YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pressure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
Page 105
78" 2" SYS. #1 & #2 SYS. #3 & #4 10" 7-1/2" POWER OPENING (4) 2-1/4" DIA. RIGGING WATER INLET (BOTH SIDES) HOLES (EACH SIDE) 10" 262-3/4" 104" WATER OUTLET 68" 89-11/16" 111-9/16" 67-7/16" 438-1/4" SIDE VIEW LD03998 YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pres- sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
Page 107
YCAS YCAS 0360 5011 1117 0360 5097 1117 1005 2438 1981 (4) 57 DIA. RIGGING 10" POWER OPENING 10" WATER INLET HOLES (EACH SIDE) (BOTH SIDES) WATER OUTLET 2642 6673 1727 2277 1713 2833 11132 SIDE VIEW LD04002 YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pressure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
Page 109
44.0" 33.9 2438 1981 SYS. #3 & #4 SYS. #1 & #2 10" POWER OPENING (4) 57 DIA. RIGGING 10" WATER INLET (BOTH SIDES) HOLES (EACH SIDE) WATER OUTLET 2642 7892 2932 1727 2277 2833 12351 SIDE VIEW LD04006 YORK INTERNATIONAL...
Site restrictions may compromise minimum clearances indicated below, resulting in unpre- dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pres- sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher than on spring isolators.
Page 111
1028 2438 1981 SYS. #3 & #4 SYS. #1 & #2 10" POWER OPENING (4) 57 DIA. RIGGING 10" WATER INLET (BOTH SIDES) HOLES (EACH SIDE) WATER OUTLET 2642 7892 2932 1727 2277 2833 12351 LD04010 SIDE VIEW YORK INTERNATIONAL...
Technical Data CLEARANCES (2 m) (1.3 m) LD04841 Notes: No obstructions allowed above the unit. Only one adjacent wall may be higher than the unit. Adjacent units should be 10 feet (3 meters) apart. FIG. 55 – CLEARANCES YORK INTERNATIONAL...
1/4" shim ance of 1/8" between resilient washer and under- between the upper load plate and vertical uprights. side of channel cap plate. Lower the equipment on the blocking or shimmed 10. Installation is now complete. isolators. YORK INTERNATIONAL...
The high pressure oil-free vapor is fed to the air ing takes place before returning to the cooler. cooled condenser coil and fans where the heat is removed. The fully condensed liquid enters the economizer. FIG. 60 – REFRIGERANT FLOW DIAGRAM YORK INTERNATIONAL...
STATOR LOCKING OIL FILTER BOLT COVER PLATE OIL FILTER BLEED & EVACUATION POINT LIFTING LUG THREADED HOLE HEATER ECONOMIZER GAS IN DISCHARGE CASE DISCHARGE GAS OUT OIL INLET FROM CONDENSER LD03668 CODING COIL FIG. 64 – COMPRESSOR COMPONENTS YORK INTERNATIONAL...
Page 127
FORM 201.18-NM3 COMPRESSOR COMPONENTS - CONT’D LD03669 FIG. 65 – COMPRESSOR COMPONENTS YORK INTERNATIONAL...
Page 128
Technical Data COMPRESSOR COMPONENTS - CONT’D LD03670 FIG. 66 – COMPRESSOR COMPONENTS YORK INTERNATIONAL...
Page 129
FORM 201.18-NM3 COMPRESSOR COMPONENTS - CONT’D LD03671 FIG. 67 – COMPRESSOR COMPONENTS YORK INTERNATIONAL...
Page 130
Technical Data COMPRESSOR COMPONENTS - CONT’D MOTOR ROTOR / MALE ROTOR LOCKING O-RING MALE ROTOR SLIDE VALVE RELIEF O-RING RETURN VALVE SPRING SUPPORT ECONOMIZER FEMALE ROTOR SLIDE VALVE RINGS PLUG LD03672 FIG. 68 – COMPRESSOR COMPONENTS YORK INTERNATIONAL...
Page 131
BEARING CLAMP NUT REVERSE THRUST BEARING THRUST SPACER SHIM THRUST BEARINGS SPACER SHIM DISCHARGE RADIAL BEARING LIP SEAL DOWEL PIN SUPPORT RING ECONOMIZER PLUG SUPPORT RING FEMALE ROTOR RETAINING RING FEMALE INLET BEARING LD03673 FIG. 69 – COMPRESSOR COMPONENTS YORK INTERNATIONAL...
COMPANY: _______________________________ START-UP DATE : _________________________ If it is necessary to add oil, connect a YORK oil pump to the charging valve on the oil separator, CHILLER MODEL #: _______________________ but do not tighten the flare nut on the delivery tubing.
Board is in the ON position (Top 2 Key on the control panel. Check them off. pins). Damage to the chiller could result if 8. Set the Time and Date. switches are improperly programmed. 9. Program the Daily Schedule start and stop times. YORK INTERNATIONAL...
The suction temperature should be taken 6" (13 mm) less than the condensing temperature (The tempera- before the compressor suction service valve, and the ture corresponding to the condensing pressure from suction pressure is taken at the compressor suction ser- the refrigerant temperature/pressure chart). vice valve. YORK INTERNATIONAL...
Motor Gas Temp = 90°F (32°C) load and unload to control water temperature, the chiller minus Economizer Press is ready to be placed into operation. 139 PSIG converted to Temp - 78°F (26°C) 12°F (6°C) YORK INTERNATIONAL...
This key is used for display and programming of the chiller operational settings and limits. This switch shuts down the entire chiller when placed in the OFF position. The switch must be ON for the chiller to operate. YORK INTERNATIONAL...
Board(s). sunlight. External interface is available for control of the chiller Displays will be updated every two seconds by the mi- via a YORK ISN System or YORK Remote Control croprocessor. Center. In addition, EMS/BAS System connections are YORK INTERNATIONAL...
The battery backup assures that Expansion Board which multiplexes them and then any programmed values (setpoints, clock, cutouts, etc.) feeds them to the Microprocessor Board. are not lost during a power failure or shutdown period regardless of the time involved. YORK INTERNATIONAL...
One Relay Output Board per system operates the mo- via the I/O Expansion Board allowing the microproces- tor contactors/starters, solenoid valves, and heaters sor to monitor motor currents for low current, high cur- which control system operation. rent, unbalanced current, and single phasing. YORK INTERNATIONAL...
This allows the micro to tional details on the Motor Protector monitor current and shut a system down if low or high Module can be found on page 16. motor current is sensed. This is a non-adjustable pro- YORK INTERNATIONAL...
Page 141
FORM 201.18-NM3 29119A SIDE VIEW 29121A 29121A TOP VIEW TOP VIEW DISPLAY SWITCH PUSHED TO LEFT INDICATES 29120A SIDE VIEW FIG. 70 – MOTOR PROTECTOR YORK INTERNATIONAL...
Motor Current Key (see Section vice must be suppressed with a sup- 3.5). However, if this display is being pressor YORK Part Number 031- viewed when the reset pulse occurs, the 00808-000 (60Hz models) or a stan- setpoint will not change on the display.
Page 143
30 seconds from the end of the last PWM signal, but must be refreshed pressed with a suppressor YORK Part before 30 minutes has elapsed. After 30 minutes, if no Number 031-00808-000 (60Hz models)
NOTE : Dimple is positioned at top edge Dip Switch Set (8 switches) System Switches S2 = System 1 S3 = System 2 S2 to S5 S4 = System 3 S5 = System 4 FIG. 71 – COMPONENT LAYOUT YORK INTERNATIONAL...
150 °F (66°C) and will turn on when the discharge tem- tem or if power is lost to the control panel. The internal perature is equal to or less than 150 °F (66°C). contacts are normally open (N.O.) and will close when YORK INTERNATIONAL...
MANUAL Lead/Lag selection will be automatically cal equipment) and the alarm circuit overridden by the micro to allow the lag compressor to should fail to function, YORK will not automatically become the lead anytime the selected lead be liable for damages.
R U N N I N G amples of each display. In each example “#” is used as This message indicates that the respective compressor applicable to represent the system number where mes- is running due to demand. sages apply to individual systems. YORK INTERNATIONAL...
S Y S P U M P I N G D O W N Permissive message will be displayed and the indicated S Y S P U M P I N G D O W N system will not run. YORK INTERNATIONAL...
For the first 3 minutes that the saturated suction tem- safety thresholds. This avoids total loss of cooling perature is at or below 29°F (-2°C) any further compres- resulting from a lockout by a safety control. YORK INTERNATIONAL...
Closure of the flow switch(es) is monitored to check fault will clear when ambient temperature rises 2°F that flow is present in the evaporator when a compres- (1°C) above the cut-out. sor is running. Any external cycling devices fitted by YORK INTERNATIONAL...
This safety is activated after 3 minutes of operation. while manually allowing repetitive re- Oil pressure must be less than 65 PSID (4.4 bar) for starts may cause further expensive R22 models as long as the compressor continues to damage to the system. run. YORK INTERNATIONAL...
Page 153
After 225 seconds of operation with suction pressure perature is above 225°F (107°C) for more than 3 sec- operating above the cut-out, a 30 second transient timer onds, the compressor will shut down. prevents short term fluctuations in suction pressure due YORK INTERNATIONAL...
Page 154
Auto restart will not occur since compressor operation. The system will be shut down if manual reset is required. A fault lockout will automati- average motor current exceeds 115% FLA. cally occur after the micro attempts 2 more starts with YORK INTERNATIONAL...
330 PSIG (23 bar) and the cutout con- occur with the corresponding auto- tacts close. A fault lockout will result if safety thresh- matic printout. This is not a cause for olds are exceeded three times in a 90 minute period. concern. YORK INTERNATIONAL...
M C H L T 4 3 . 8 ° indicate the actual values are greater than or less than the values which are being displayed, but are outside the ability of the micro to give an actual reading. This YORK INTERNATIONAL...
MOTOR CURRENT KEY solenoid in the form of a current signal. To the micro- processor, STEP 0 = fully unloaded and STEP 75 = Pressing the Motor Current key displays compressor fully loaded. current for each system: YORK INTERNATIONAL...
20 to 70 PSIG (1 to 5 bar) for R-22 models and 5 to 70 PSIG (0.3 to 5 bar) for R-407c models. The Options key provides a display of options which are programmed by the positions of the S1 Dip Switches YORK INTERNATIONAL...
Page 159
The R-22 Mode MUST be selected for models using LD03511A refrigerant type R-22. Incorrect selection of this switch FIG. 74 – ENLARGED PHOTOGRAPH OF DIP may cause serious damage to the chiller. SWITCHES ON MICROPROCESSOR BOARD YORK INTERNATIONAL...
Control Control sage. Refrigerant R-407C Refrigerant R-22 Spare Spare The following keys can be scrolled using the Function Spare Spare Key: Chilled Liquid Temps, System # Data, Motor Spare Spare Current and Options. Spare Spare Spare Spare YORK INTERNATIONAL...
“rate control” printer. As the data is transmitted it is erased from the and “temperature deviation from setpoint” to determine memory. when loading should occur. YORK INTERNATIONAL...
The follow text shows a typical example printout ob- CUR/TEMP – EMS PWM Current Limiting & tained by pressing the Operating Data key with an op- Temperature Reset Enabled tional printer attached. In this case an example is shown YORK INTERNATIONAL...
Page 163
YCAS 4 System models provide similar printouts SYSTEM 2 DATA for the appropriate number of systems: COMPRESSORS STATUS RUN TIME 0- 0-15-26 D-H-M-S MOTOR CURRENT 104 AMPS 87 %FLA YORK INTERNATIONAL CORPORATION SUCTION PRESSURE 57 PSIG MILLENNIUM SCREW CHILLER DISCHARGE PRESSURE 233 PSIG OIL PRESSURE...
This message displays the suction pressure cut-out pro- grammed at the time of the fault. S H U T D O W N O C C U R R E D 5 : 5 9 A M N O V YORK INTERNATIONAL...
Page 165
This message shows the Run Time logged on the sys- tem since the last compressor start, in Days (D), Hours (H), Minutes (M), and Seconds (S). YORK INTERNATIONAL...
Page 166
System 3 data before looping back to the start of the Safety Shutdown display. This message, which is only displayed if the unit is in R-407c mode, indicates the refrigerant temperature at the inlet of the cooler. YORK INTERNATIONAL...
4 compressor models will be similar. COMPRESSOR HEATER WYE-DELTA RELAY An example of the HISTORY Printout is shown below: SYSTEM 2 DATA YORK INTERNATIONAL CORPORATION COMPRESSORS STATUS RUN TIME 0- 0-15-26 D-H-M-S MILLENNIUM SCREW CHILLER MOTOR CURRENT 104 AMPS 87 %FLA...
“AM” or “PM” on the display. For ex- ample, pressing the â key when the cursor is on “PM” the original values will be returned. changes it to “AM.” YORK INTERNATIONAL...
(+ or - Range) This deviation temperature error and the rate of change to determine is simply called the “Control Range” and is best de- the amount of loading necessary to cool the chilled liq- YORK INTERNATIONAL...
Page 170
Load Timers are always set at 10 seconds first. between changes. On 4 compressor chillers, loading will operate the same Unload timers are set at 5 seconds between as a 3 compressor chiller with another compressor added changes. YORK INTERNATIONAL...
Page 171
2°F below the low limit of the Steps. Under these circumstances, the two systems will Control Range (CR), b) if chilled liq- not appear to equalize loading. uid temperature drops more than CR/ 2 below the low limit of the Control Range. YORK INTERNATIONAL...
10°F (or 10°C). Press the ENTER Key to memory. store the new value in memory. After pressing the Enter key, the display will continue to show the message until another key is pressed. YORK INTERNATIONAL...
Press ENTER to move on to the hour part of the display. Next, key in the time (hours/minutes) using a leading “0” ing the Set Time key a second time enters “display” mode in which the cursor will disappear and the “live” clock will be displayed. YORK INTERNATIONAL...
ON position, all 00.00s should be programmed into quirements are occur only the daily schedule. This can be done manually for indi- occasionally. vidual days or for all days by pressing Cancel and En- ter for the Monday Start/Stop schedule. YORK INTERNATIONAL...
Daily Schedule. Once activated, Manual Override is Section 2.5. only active for a period of 30 minutes and the follow- ing status message will be observed. M A N U A L O V E R R I D E YORK INTERNATIONAL...
Enter key the first 5 seconds of operation after which if the cut- is pressed and the display will scroll on to the next pro- out point is exceeded for 3 seconds, the system will grammable value. shut down. YORK INTERNATIONAL...
Page 177
5 - 70 PSIG (0.3 bar) for tion at low refrigerant suction pressure. R22 and R-407c models. In this mode, the cutout should YORK INTERNATIONAL...
Page 178
Values below 25°F (-4°C) can be sor, if current draw approaches the maximum limit cut- used for applications requiring chiller operation at YORK INTERNATIONAL...
Page 179
Al- though the minimum setting allowed on this timer will Manual lead/lag. The ENTER key must be pressed to avoid excessive heat build up, adjusting the timer for save the selection in memory. YORK INTERNATIONAL...
PROGRAM key followed by the ENTER key, to Leaving Chilled Liquid Temp Cut-Out 36°F (2°C) program the “refrigerant type.” Press the Program key Suction Pressure Cut-Out 44 PSIG (3 bar) again, key in the numbers “6140”, then press Enter. As YORK INTERNATIONAL...
13, 15, 17, 19 >290 PSIG <220 PSIG & <85°F 21M, 22M, 23M, 24M 330, 331, 332 8, 9, 10 * Newer versions of EPROMs will have ON and OFF pressures 15 PSIG below the published values shown above. YORK INTERNATIONAL...
Page 182
15M, 16M, 17M, 18M, 19M 230, 231, 232 10, 14, 15 SYSTEM 3 IS ALWAYS EQUIPPED WITH 4 FANS. * Newer versions of EPROMs will have ON and OFF pressures 15 PSIG below the published values shown above. YORK INTERNATIONAL...
14, 16, 18, 20 >290 PSIG <220 PSIG & <85°F 27M, 28M, 29M, 30M 430, 431, 432 8, 9, 10 * Newer versions of EPROMs will have ON and OFF pressures 15 PSIG below the published values shown above. YORK INTERNATIONAL...
Page 184
9, 10 14, 16, 18 >290 PSIG <220 PSIG & <85°F 27M, 28M, 29M 430, 431, 432 8, 9, 10 * Newer versions of EPROMs will have ON and OFF pressures 15 PSIG below the published values shown above. YORK INTERNATIONAL...
LOAD’ for approximately half an hour. The oil level YORK shall not be liable for costs incurred to return should be about half way up the upper of the two sight the unit to satisfactory condition.
YORK Order No. ________________________ CHILLER/COMPRESSOR Compr. Ser. No. _________________________ Operating Log Unit Ser. No. ___________________________ Refrigerant ____________________________ Date Time Hour Meter Reading Equipment Room Temp./Outdoor Temp. Suction Pressure Suction Temperature Suction Superheat Discharge Pressure Actual Discharge Temperature Oil Pressure Oil Temperature...
* Reserved for customer use for any special site determined requirements. This procedure must be performed at the specified time interval by an Industry Certified Technician who has been trained and qualified to work on this type of YORK equipment. A record of this procedure being successfully carried out must be maintained on file by the equipment owner should proof of adequate maintenance be...
BMLT 025-29964-000 Other spare parts vary depending on the unit model. Contact your local YORK Sales and Service Center for information and please quote the unit model number and serial number. When ordering spare parts, we will require the follow-...
Check that the compressor unloads correctly. Measured temperature is incorrect. Check sensor calibration, location and wiring. Chiller FAULT: VAC Check mains supply is stable and within allowable UNDERVOLTAGE Poor mains supply voltage. limits. displayed. Check for voltage dip on compressor start. YORK INTERNATIONAL...
Page 191
Check operation of economizer and motor cooling TEV’s and liquid solenoid valve. SYS # CURR LIMITING High compressor motor current has Check if liquid temperature is within operating limits. displayed activated unloading. Check if ambient air temperature is above operating (Compressor current limits. unloading.) YORK INTERNATIONAL...
Subject has been received by YORK. to the exclusions listed below, YORK, at its option, will repair or replace, FOB point of shipment, such YORK ALL WARRANTIES AND GUARANTEES ARE VOID IF: products or components as it finds defective.