Dimensions; Ycas02830 - 0343 (Si) - York MILLENIUM YCAS Series Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

Technical Data
83
178
229
127
432
POWER ENTRY
(8) 38,51,64 CONDUIT K.O.'S
POWER: MULTIPLE POINT WITH TERMINAL BLOCKS
NOTES:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance,
reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre-
dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high
pressure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control
center assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m;
control panel end to wall - 1.2m; top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall
may be higher than the unit.
72
DIMENSIONS – YCAS0283-0343 (SI)
3 SPA. @ 127
89
127
44
432
25 TYP.
CONTROL ENTRY
(7) 13 CONDUIT K.O.'S
VIEW B-B
C
B
CONTROL
TRANSFORMER
SERVICE SWITCH
43
VIEW A-A
57
229
CONTROL ENTRY
(8) 22 DIA. HOLES
MICRO-COMPUTER
CONTROL CENTER
OPTIONS PANEL
C
B
438
49 (EDGE OF
UNIT TO COOLER
2235
CONNECTION)
2321
LD04478
25 TYP.
51
51
25
VIEW C-C
LD04477