Anti-Recycle Timer; Anti-Coincidence Timer; Evaporator Pump Control; Compressor Heater Control - York MILLENIUM YCAS Series Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

1.13

ANTI-RECYCLE TIMER

The programmable Anti-Recycle Timer allows the user
to select the compressor anti-recycle time to best suit
their needs. Motor heating is a result of inrush current
when the motor is started. This heat must be dissipated
before another start takes place or motor damage may
result. The anti-recycle timer assures that the motor has
sufficient time to cool before it is restarted.
An adjustable timer allows for the motor cooling, but
gives the user the ability to extend the anti-recycle timer
to cut down on cycling. In some applications, faster
compressor start response is necessary and shorter anti-
recycle times are required. These needs should be kept
in mind but whenever possible the timer should be ad-
justed for the longest period of time tolerable. 600 sec-
onds is recommended, although 300 seconds provides
adequate motor cooling time. Longer periods will al-
low more heat dissipation, reduce cycling, and possi-
bly increase motor life. See Section 8.2, page 140 for
programming of the anti-recycle timer.
1.14

ANTI-COINCIDENCE TIMER

The Anti-Coincidence Timer assures that 2 systems
do not start simultaneously. This assures that inrush
current is kept to a minimum. A 60 second time delay
will always separate motor starts. This timer is not
programmable.
1.15

EVAPORATOR PUMP CONTROL

Dry contacts are provided which transition (close) when
the Daily Schedule is calling for chiller operation and
power has been applied to the Micro Panel for 30 sec-
onds. If for some reason the evaporator pump contacts
have been closed to run the pump and a power loss or
Daily Schedule shuts the pump down (contacts open),
the contacts will not reclose for any reason until 30
seconds has elapsed after power re-application or 30
seconds have elapsed between a Daily Schedule shut-
down and restart.
1.16

COMPRESSOR HEATER CONTROL

Each compressor has its own heater. The heater will be
off whenever the compressor is running. As soon as the
compressor shuts off, the heater will turn on and stay
on for 5 minutes. After 5 minutes has elapsed, the heater
will shut off if the discharge temperature rises above
66°C (150 °F) and will turn on when the discharge tem-
perature is equal to or less than 66°C (150 °F).
YORK INTERNATIONAL
1.17

EVAPORATOR HEATER CONTROL

The evaporator heater is controlled by ambient tem-
perature. When the ambient temperature drops below
4°C (40°F), the heater is turned on when the compres-
sors are turned off. When the temperature rises above
7°C (45°F), the heater is turned off. An undervoltage
condition will keep the heater off until full voltage is
restored to the system. The heater will provide freeze
protection to -28°C (-20°F).
115VAC power must remain "ON"
through CB3 for freeze protection.
Otherwise, the evaporator must be
drained.
1.18

PUMPDOWN (LLSV) CONTROL

Each compressor undergoes a pump down cycle on start-
up and shutdown. This assures that liquid refrigerant
does not enter the compressor on start-up, eliminating
the need for recycling pump down, saving energy and
reducing compressor starts and wear.
On start-up, the controls unload the compressor and the
system either pumps down to the low suction pressure
cutout setting or pumps down for 15 seconds, which-
ever comes first, after which the Liquid Line Solenoid
Valve is energized and normal operation commences.
On shutdown, the microprocessor controls unload the
compressor and the Liquid Line Solenoid Valve and
Economizer/Motor Cooling Liquid Supply Solenoid
Valve are de-energized. The compressor continues to
operate until it either pumps down to the low suction
pressure cutout setting or for 180 seconds, whichever
comes first. Pump down occurs on "normal" shutdowns
where cooling demand has been satisfied or when a
system switch is turned off, a flow switch opens, run
permissive is lost or a Daily Schedule or a Remote Shut-
down is called for.
No pumpdown will occur on a safety shutdown. See
page 111 for the pumpdown display message.
1.19

ALARMS

Internal contacts are provided in the Power Panel (See
Section 1.12) which can be used to remotely signal a
warning whenever a fault lockout occurs on any sys-
tem or if power is lost to the control panel. The internal
contacts are normally open (N.O.) and will close when
FORM 201.18-NM6
8
107

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents