CAUTION:
No Controls (relays, etc.)
should be mounted in the
Smart Panel enclosure or
connected to power sup-
plies in the control panel.
Additionally, control wir-
ing not connected to the
Smart Panel should not be
run through the cabinet.
This could result in nui-
sance faults.
CAUTION:
Any inductive devices (re-
lays) wired in series with
the flow switch for start/
stop, in the Alarm cir-
cuitry, or pilot relays for
pump starters wired
through motor contactor
auxiliary contact must be
suppressed with YORK
P/N 031-00808-000 sup-
pressor across the relay/
contactor coil.
Any contacts connected to
flow switch inputs or BAS
inputs on terminals, must
be suppressed with a
YORK P/N 031-00808-000
suppressor across the re-
lay/contactor coil.
CAUTION:
Control wiring connected
to the control panel
should never be run in
the same conduit power
wiring.
61