Using The Pulse Train Output; Terminal A2 Input Signal Selection - YASKAWA E1000 Technical Manual

For fan and pump
Table of Contents

Advertisement

◆ Using the Pulse Train Output

The pulse train output terminal MP can either supply power but can also be used with external power supply. Peripheral
devices should be connected in accordance with the specifications listed below. Failure to do so can cause unexpected
drive operation, and can damage the drive or connected circuits.
Using Power from the Pulse Output Terminal (Source Mode)
The high voltage level of the pulse output terminal depends on the load impedance.
Load Impedance R
Note: The load resistance needed in order to get a certain high level voltage V
Figure 3.37
Using External Power Supply (Sink Mode)
The high voltage level of the pulse output signal depends on the external voltage applied. The voltage must be between
12 and 15 Vdc. The load resistance must be adjusted so that the current is lower than 16 mA.
External Power Supply (V)
12 to 15 Vdc ±10%
Figure 3.38

◆ Terminal A2 Input Signal Selection

Terminal A2 can be used to input either a voltage or a current signal. Select the signal type using switch S1 as explained
in
Table
3.18. Set parameter H3-09 accordingly as shown in
Board on page 85
for locating switch S1.
Note: If terminals A1 and A2 are both set for frequency bias (H3-02 = 0 and H3-10 = 0), both input values will be combined to create
the frequency reference.
Setting
V (left position)
I (right position) (default)
No.
Parameter Name
H3-09
Terminal A2 signal level selection
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
(kΩ)
L
1.5 kΩ
4 kΩ
10 kΩ
MP
AC
Figure 3.31 Pulse Output Connection Using Internal Voltage Supply
External Power Supply
MP
AC
Figure 3.32 Pulse Output Connection Using External Voltage Supply
Table 3.12 DIP Switch S1 Settings
Table 3.13 Parameter H3-09 Details
Selects the signal level for terminal A2.
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
3: 0 to 20 mA
Output Voltage V
can be calculated by:
MP
Load Impedance
V
R
MP
L
Load Impedance
Sink Current
Table
3.19. Refer to
Switches and Jumpers on the Terminal
Description
Voltage input (-10 to +10 V)
Current input (4 to 20 mA or 0 to 20 mA): default setting
Description
3.10 Control I/O Connections
(V) (insulated)
MP
5 V
8 V
10 V
R
= V
2 / (12 - V
)
L
MP
MP
Load Impedance (kΩ)
1.0 kΩ or higher
Setting
Range
0 to 3
3
Default
Setting
2
87

Advertisement

Table of Contents
loading