Setting 4: Hvac Fan Application; Setting 5: Compressor Application - YASKAWA E1000 Technical Manual

For fan and pump
Table of Contents

Advertisement

4.6 Application Selection
No.
b1-01
Frequency Reference Selection
b1-02
Run Command Selection
b1-04
Reverse Operation Selection
b3-01
Speed Search Selection at Start
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
E1-03
V/f Pattern Selection

◆ Setting 4: HVAC Fan Application

No.
A1-02
Control Method Selection
b1-04
Reverse Operation Selection
b1-17
Run Command at Power Up
C6-02
Carrier Frequency Selection
H2-03
Terminals M5,M6 Function Selection
L2-01
Momentary Power Loss Operation Selection
L8-03
Overheat Pre-Alarm Operation Selection
L8-38
Carrier Frequency Reduction
No.
b1-01
Frequency Reference Selection
b1-02
Run Command Selection
b1-03
Stopping Method Selection
b1-04
Reverse Operation Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
C6-02
Carrier Frequency Selection
d2-01
Frequency Reference Upper Limit

◆ Setting 5: Compressor Application

No.
A1-02
Control Method Selection
b1-04
Reverse Operation Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
E1-03
V/f Pattern Selection
L2-01
Momentary Power Loss Operation Selection
L3-04
Stall Prevention Selection during Deceleration
No.
b1-01
Frequency Reference Selection
b1-02
Run Command Selection
b1-04
Reverse Operation Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
112
Table 4.8 Exhaust Fan: User Parameters (A2-01 to A2-16)
Parameter Name
Table 4.9 HVAC Fan: Parameter Settings
Parameter Name
Table 4.10 HVAC Fan: User Parameters (A2-01 to A2-16)
Parameter Name
Table 4.11 Compressor: Parameter Settings
Parameter Name
Table 4.12 Compressor: User Parameters (A2-01 to A2-16):
Parameter Name
No.
E1-07
Mid Output Frequency
E1-08
Mid Output Frequency Voltage
E2-01
Motor Rated Current
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
L5-01
Number of Auto Restart Attempts
0: V/f Control
1: Reverse Prohibited
1: Run command issued, motor operation start
3: 8.0 kHz
39: Watt Hour Pulse Output
2: CPU Power Active - Drive will restart if power returns prior to control power
supply shut down.
4: Operation at lower speed
2: Enabled across entire frequency range.
No.
d2-02
Frequency Reference Lower Limit
E1-03
V/f Pattern Selection
E1-04
Max Output Frequency
E2-01
Motor Rated Current
H3-11
Terminal A2 Gain Setting
H3-12
Terminal A2 Input Bias
L2-01
Momentary Power Loss Operation Selection
o4-12
kWh Monitor Initial Value Selection
0: V/f Control
1: Reverse Prohibited
5.0 s
5.0 s
0FH
1: Enabled
1: Enabled
No.
E1-03
V/f Pattern Selection
E1-07
Mid Output Frequency
E1-08
Mid Output Frequency Voltage
E2-01
Motor Rated Current
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
Parameter Name
Default Setting
Parameter Name
Default Setting
Parameter Name