General Description; General Description; E1000 Model Selection - YASKAWA E1000 Technical Manual

For fan and pump
Table of Contents

Advertisement

1.2

General Description

◆ E1000 Model Selection

Table 1.1
gives a reference for drive selection depending on the motor power.
Note: The models and capacities in shown here are based on standard settings and operation conditions. Derating is required for higher
carrier frequencies and higher ambient temperatures.
Motor Power
(kW)
Model CIMR-E
0.75
2A0004
1.1
2A0006
1.5
2A0008
2.2
2A0010
3.0
2A0012
3.7
2A0018
5.5
2A0021
7.5
2A0030
11
2A0040
15
2A0056
18.5
2A0069
22
2A0081
30
2A0110
37
2A0138
45
2A0169
55
2A0211
75
2A0250
90
2A0312
2A0360
110
2A0415
132
160
185
220
250
355
500
630
Note: Current derating is required when setting the carrier frequency higher.
details.
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
Table 1.1 E1000 Models
Three-Phase 200 V Class
Rated Output Current (A)
3.5
6
8
9.6
12
17.5
21
30
40
56
69
81
110
138
169
211
250
312
360
415

1.2 General Description

Three-Phase 400 V Class
Model CIMR-E
4A0002
4A0004
4A0005
4A0007
4A0009
4A0011
4A0018
4A0023
4A0031
4A0038
4A0044
4A0058
4A0072
4A0088
4A0103
4A0139
4A0165
4A0208
4A0250
4A0296
4A0362
4A0414
4A0515
4A0675
4A0930
4A1200
Refer to Carrier Frequency Derating on page 354
Rated Output Current (A)
2.1
4.1
5.4
6.9
8.8
11.1
17.5
23
31
38
44
58
72
88
103
139
165
208
250
296
362
414
515
675
930
1200
for
1