5.2 b: Application
b3-18: Speed Search Restart Detection Time
Sets the time that the current must be greater than the level set in b3-17 before Speed Search can be restarted.
No.
b3-18
b3-19: Number of Speed Search Restarts
Sets the number of times the drive should attempt to find the speed and restart the motor. If the number of restart attempts
exceeds the value set to b3-19, the SEr fault will occur and the drive will stop.
No.
b3-19
b3-24: Speed Search Method Selection
Sets the Speed Search method used.
No.
b3-24
Setting 0: Current Detection Speed Search
Setting 1: Speed Estimation Speed Search
Note: For explanations of the Speed Search methods,
Speed Estimation Type Speed Search (b3-24 = 1) on page
b3-25: Speed Search Wait Time
Sets the wait time between Speed Search restarts. Increase the wait time if problems occur with overcurrent, overvoltage,
or if the SEr fault occurs.
No.
b3-25
b3-27: Start Speed Search Select
Selects a condition to activate Speed Search Selection at Start (b3-01) or External Speed Search Command 1 or 2 from
the multi-function input.
No.
b3-27
Setting 0: Triggered when a Run Command is Issued (Normal)
Setting 1: Triggered when an External Baseblock is Released

◆ b4: Delay Timers

The timer function is independent of drive operation and can be used to delay the switching of a digital output triggered
by a digital input signal. An on-delay and off-delay can be separately set. The delay timer can help to get rid of chattering
switch noise from sensors.
To enable the timer function, a multi-function input must be set to "Timer input" (H1-=18) and a multi-function
output must be set to "Timer output" (H2-=12). One timer can be used only.
b4-01, b4-02: Timer Function On-Delay, Off-Delay Time
b4-01 sets the on-delay time for switching the timer output. b4-02 sets the off-delay time for switching the timer output.
No.
b4-01
b4-02
144
Name
Speed Search Restart Detection Time
Name
Number of Speed Search Restarts
Parameter Name
Speed Search Method Selection
Refer to Current Detection Speed Search (b3-24 = 0) on page 139
140.
Name
Speed Search Wait Time
Parameter Name
Start Speed Search Select
Name
Timer Function On-Delay Time
Timer Function Off-Delay Time
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
Setting Range
0.00 to 1.00 s
Setting Range
0 to 10
Setting Range
0 or 1
and
Refer to
Setting Range
0.0 to 30.0 s
Setting Range
0, 1
Setting Range
0.0 to 3000.0 s
0.0 to 3000.0 s
Default
0.10 s
Default
3
Default
0
Default
0.5 s
Default
0
Default
0.0 s